| 2014-01-28 15:02:30 | PLUMBING PLAN REVIEW |
| | PERMIT: 13121076 |
| | ADD: 8151 OKEECHOBEE BLVD |
| | CONT: P & T CONSTRUCTION |
| | TEL: (561)324-8055 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | ARCHITECT: TERCILLA COURTEMANCHE 561-478-4457 |
| | RENE TERCILLA |
| | |
| | RGD CONSULTING ENGINEERS 561-743-0165 |
| | P. E. MICHAEL J. BISHOP |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JAN. 28/2014 |
| | ACTION: DENIED |
| | |
| | 1) THE LS1.1 & LS1.2 SHEETS PROVIDE SQUARE FOOTAGE PER |
| | ROOM BUT THEY DO NOT PROVIDE THE OCCUPANT LOADS. PLEASE |
| | PROVIDE A BREAK DOWN PER ROOM AND FLOOR AND PROVIDE |
| | COMPLIANCE WITH SECTION 403 & TABLE 403.1 2010 |
| | FBC-PLUMBING. T. C. PROVIDED THE OCCUPANT LOAD COUNT BY |
| | PHONE FOR THE 1ST AND 2ND FLOOR AS FOLLOWS; |
| | |
| | 1ST FLOOR 888 OCCUPANTS |
| | 2ND FLOOR 943 OCCUPANTS |
| | |
| | 1ST FLOOR & 2ND FLOOR ARE OK FOR WATER CLOSETS, |
| | LAVATORIES WHEN 1ST & 2ND FLOOR COMBINED MEET THE |
| | REQUIED 38. |
| | |
| | 1ST FLOOR DRINKING FOUNTAINS MEET THE REQUIRED 9 AND |
| | THE 1 REQUIRED SERVICE SINK. |
| | |
| | 2ND FLOOR DRINKING FOUNTAINS REQUIRED 943/100= 10 |
| | DRINKING FOUNTAINS THERE ARE ONLY 5 ON THE 2ND FLOOR, |
| | AND THE 1 REQUIRED SERVICE SINK NONE PROVIDED, PROVIDE |
| | COMPLIANCE WITH SECTION 403 & TABLE 403.1 2010 |
| | FBC-PLUMBING.COMPLIED, |
| | |
| | |
| | 2) SHEET P1.1: |
| | |
| | 2A) SEE 2 INCH SANITARY ON BETWEEN GRID LINES 8.4/ 9.0 |
| | & B.9 /C.1 THE CONNECTION INTO THE 4 INCH SANITARY IS |
| | TURNED TO GO AGAINST THE FLOW. |
| | |
| | 2B) INFORMATIONA ONLY,L NO RESPONCE REQUIRED. THE |
| | GREASE TRAP INFORMATION HAS BEEN PROVIDED ON SHEET P6.2 |
| | FOR SIZING BUT WILL REQUIRE A SEPERATE PERMIT. |
| | INFORMATION PROVIDED ON SIZING; |
| | MARK: GT-1 SCHIER MODEL PATG-30-LO INDOOR |
| | UNIT MAX FLOW RATE 30 |
| | LIQUID CAP. 23 GALLONS |
| | MAX. GREASE CAPACITY 90 POUNDS |
| | 3" INLET & OUTLET |
| | |
| | 2C) THE PLANS INDICATE FLOOR SINK (FS-2) INFRONT OF |
| | WHAT APPEARS TO BE A OVEN, THE ELECTRICAL CIRCUIT |
| | BREAKERS SHOW ICE MACHINE, FREEZERS, REFRIGARATORS |
| | WHERE ARE THESE UNITS TO DRAIN? SEE FBC-P TABLE 709.2. |
| | |
| | 2D) THE PLANS INDICATE WHAT APPEARS TO BE WALK IN |
| | REFRIGARATOR AND FREEZER, ARE THEY GOING TO HAVE FLOOR |
| | DRAINS INSIDE THE UNITS, FLOOR DRAINS LOCATED WITHIN |
| | WALK-IN REFRIGERATORS OR FREEZERS IN FOOD SERVICE AND |
| | FOOD ESTABLISHMENTS SHALL BE INDIRECTLY CONNECTED TO |
| | THE SANITARY DRAINAGE SYSTEM BY MEANS OF AN AIR GAP. |
| | WHERE A FLOOR DRAIN IS LOCATED WITHIN AN AREA SUBJECT |
| | TO FREEZING, THE WASTE LINE SERVING THE FLOOR DRAIN |
| | SHALL NOT BE TRAPPED AND SHALL INDIRECTLY DISCHARGE |
| | INTO A WASTE RECEPTOR LOCATED OUTSIDE OF THE AREA |
| | SUBJECT TO FREEZING. 802.1.2 FLOOR DRAINS IN FOOD |
| | STORAGE AREAS. |
| | |
| | 2E) THE PLANS DO NOT INDICATE ANY DISHWASHING |
| | FACILITIES, 802.1.7 COMMERCIAL DISHWASHING MACHINES. |
| | THE DISCHARGE FROM A COMMERCIAL DISHWASHING MACHINE |
| | SHALL BE THROUGH AN AIR GAP OR AIR BREAK INTO A |
| | STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION |
| | 802.2 2010 FBC-P. IF A COMMERCIAL DISHWASHING MACHINE |
| | IS TO BE INSTALLED WE WILL NEED THE CUT SHEET ON THE |
| | FLOW RATE TO ADD TO THE GREASE TRAP LOADING. |
| | |
| | 2F) THE PLANS ALSO INDICATE A ELEVATOR SUMP WITH OIL |
| | DETECTOR, PLEASE PROVIDE THE MANUFACTURERS CUT SHEETS |
| | TO DETERMINE CODE COMPLIANCE WITH SECTION; 1003.4 OIL |
| | SEPARATORS REQUIRED. THE EXCEPTION: AN OIL SEPARATOR IS |
| | NOT REQUIRED IN HYDRAULIC ELEVATOR PITS WHERE AN |
| | APPROVED ALARM SYSTEM IS INSTALLED. WE WILL NEED THE |
| | CUT SHEETS AND ALSO NEED TO SEE WHERE THE OIL DETECTOR |
| | IS TIED INTO AN ALARM SYSTEM. |
| | |
| | 3) SHEET P2.1 |
| | 3A) THERE WERE NO CIVIL PLANS SUBMITTED UNDER THIS |
| | REVIEW. NOTE #1 INDICATES BACKFLOW REGULATOR TO BE |
| | PROVIDED BY OTHERS, PLEASE PROVIDE CODE COMPLIANCE WITH |
| | 2010 FBC-P 608.3 DEVICES, APPURTENANCES, APPLIANCES AND |
| | APPARATUS. ALL DEVICES, APPURTENANCES, APPLIANCES AND |
| | APPARATUS INTENDED TO SERVE SOME SPECIAL FUNCTION, SUCH |
| | AS STERILIZATION, DISTILLATION, PROCESSING, COOLING, OR |
| | STORAGE OF ICE OR FOODS, AND THAT CONNECT TO THE WATER |
| | SUPPLY SYSTEM, SHALL BE PROVIDED WITH PROTECTION |
| | AGAINST BACKFLOW AND CONTAMINATION OF THE WATER SUPPLY |
| | SYSTEM. WATER PUMPS, FILTERS, SOFTENERS, TANKS, |
| | COMMERCIAL DRINKING WATER DISPENSERS AND ALL OTHER |
| | APPLIANCES AND DEVICES THAT HANDLE OR TREAT POTABLE |
| | WATER SHALL BE PROTECTED AGAINST CONTAMINATION. |
| | |
| | 3B) NOTE NUMBER 6 PROVIDE WATER HAMMER ARESTOR, REF |
| | GENERAL PLUMBING NOTES, WHERE ? PROVIDE COMPLIANCE WITH |
| | 2010 FBC-P 604.9 WATER HAMMER. |
| | THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM |
| | SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER |
| | HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED |
| | WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER |
| | ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE |
| | MANUFACTURER?S SPECIFICATIONS. WATER-HAMMER ARRESTORS |
| | SHALL CONFORM TO ASSE 1010. |
| | |
| | 4) PLEASE PROVIDE COMPLIANCE ALL HOSE BIBBS TO HAVE |
| | BACK FLOW PREVENTORS 2010 FBC-P 608.1 & TABLE 608.1. |
| | |
| | 5) SHEET P6.2 JANITORS SINK INDICATES THE FAUCET TO |
| | HAVE THREADED HOSE CONNECTION, PROVIDE COMPLIANCE WITH |
| | 2010 FBC-P 424.6 HOSE-CONNECTED OUTLETS. |
| | FAUCETS AND FIXTURE FITTINGS WITH HOSE-CONNECTED |
| | OUTLETS SHALL CONFORM TO ASME A112.18.3M OR CSA B125. |
| | |
| | 6) SHEET P3.1 THE TEACHER'S LOUNGE SECOND FLOOR SINK |
| | DOESN'T APPEAR TO HAVE A VENT, THIS SINK WILL NEED TO |
| | COMPLY WITH FBC-P 907.1 INDIVIDUAL VENT. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |