Plan Review Notes
Plan Review Notes For Permit 13121076
Permit Number 13121076
Review Stop P
Sequence Number 1
Notes
Date Text
2014-01-28 15:02:30PLUMBING PLAN REVIEW
 PERMIT: 13121076
 ADD: 8151 OKEECHOBEE BLVD
 CONT: P & T CONSTRUCTION
 TEL: (561)324-8055
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 ARCHITECT: TERCILLA COURTEMANCHE 561-478-4457
 RENE TERCILLA
  
 RGD CONSULTING ENGINEERS 561-743-0165
 P. E. MICHAEL J. BISHOP
  
 1ST REVIEW
 DATE: TUES. JAN. 28/2014
 ACTION: DENIED
  
 1) THE LS1.1 & LS1.2 SHEETS PROVIDE SQUARE FOOTAGE PER
 ROOM BUT THEY DO NOT PROVIDE THE OCCUPANT LOADS. PLEASE
 PROVIDE A BREAK DOWN PER ROOM AND FLOOR AND PROVIDE
 COMPLIANCE WITH SECTION 403 & TABLE 403.1 2010
 FBC-PLUMBING. T. C. PROVIDED THE OCCUPANT LOAD COUNT BY
 PHONE FOR THE 1ST AND 2ND FLOOR AS FOLLOWS;
  
 1ST FLOOR 888 OCCUPANTS
 2ND FLOOR 943 OCCUPANTS
  
 1ST FLOOR & 2ND FLOOR ARE OK FOR WATER CLOSETS,
 LAVATORIES WHEN 1ST & 2ND FLOOR COMBINED MEET THE
 REQUIED 38.
  
 1ST FLOOR DRINKING FOUNTAINS MEET THE REQUIRED 9 AND
 THE 1 REQUIRED SERVICE SINK.
  
 2ND FLOOR DRINKING FOUNTAINS REQUIRED 943/100= 10
 DRINKING FOUNTAINS THERE ARE ONLY 5 ON THE 2ND FLOOR,
 AND THE 1 REQUIRED SERVICE SINK NONE PROVIDED, PROVIDE
 COMPLIANCE WITH SECTION 403 & TABLE 403.1 2010
 FBC-PLUMBING.COMPLIED,
  
  
 2) SHEET P1.1:
  
 2A) SEE 2 INCH SANITARY ON BETWEEN GRID LINES 8.4/ 9.0
 & B.9 /C.1 THE CONNECTION INTO THE 4 INCH SANITARY IS
 TURNED TO GO AGAINST THE FLOW.
  
 2B) INFORMATIONA ONLY,L NO RESPONCE REQUIRED. THE
 GREASE TRAP INFORMATION HAS BEEN PROVIDED ON SHEET P6.2
 FOR SIZING BUT WILL REQUIRE A SEPERATE PERMIT.
 INFORMATION PROVIDED ON SIZING;
 MARK: GT-1 SCHIER MODEL PATG-30-LO INDOOR
 UNIT MAX FLOW RATE 30
 LIQUID CAP. 23 GALLONS
 MAX. GREASE CAPACITY 90 POUNDS
 3" INLET & OUTLET
  
 2C) THE PLANS INDICATE FLOOR SINK (FS-2) INFRONT OF
 WHAT APPEARS TO BE A OVEN, THE ELECTRICAL CIRCUIT
 BREAKERS SHOW ICE MACHINE, FREEZERS, REFRIGARATORS
 WHERE ARE THESE UNITS TO DRAIN? SEE FBC-P TABLE 709.2.
  
 2D) THE PLANS INDICATE WHAT APPEARS TO BE WALK IN
 REFRIGARATOR AND FREEZER, ARE THEY GOING TO HAVE FLOOR
 DRAINS INSIDE THE UNITS, FLOOR DRAINS LOCATED WITHIN
 WALK-IN REFRIGERATORS OR FREEZERS IN FOOD SERVICE AND
 FOOD ESTABLISHMENTS SHALL BE INDIRECTLY CONNECTED TO
 THE SANITARY DRAINAGE SYSTEM BY MEANS OF AN AIR GAP.
 WHERE A FLOOR DRAIN IS LOCATED WITHIN AN AREA SUBJECT
 TO FREEZING, THE WASTE LINE SERVING THE FLOOR DRAIN
 SHALL NOT BE TRAPPED AND SHALL INDIRECTLY DISCHARGE
 INTO A WASTE RECEPTOR LOCATED OUTSIDE OF THE AREA
 SUBJECT TO FREEZING. 802.1.2 FLOOR DRAINS IN FOOD
 STORAGE AREAS.
  
 2E) THE PLANS DO NOT INDICATE ANY DISHWASHING
 FACILITIES, 802.1.7 COMMERCIAL DISHWASHING MACHINES.
 THE DISCHARGE FROM A COMMERCIAL DISHWASHING MACHINE
 SHALL BE THROUGH AN AIR GAP OR AIR BREAK INTO A
 STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION
 802.2 2010 FBC-P. IF A COMMERCIAL DISHWASHING MACHINE
 IS TO BE INSTALLED WE WILL NEED THE CUT SHEET ON THE
 FLOW RATE TO ADD TO THE GREASE TRAP LOADING.
  
 2F) THE PLANS ALSO INDICATE A ELEVATOR SUMP WITH OIL
 DETECTOR, PLEASE PROVIDE THE MANUFACTURERS CUT SHEETS
 TO DETERMINE CODE COMPLIANCE WITH SECTION; 1003.4 OIL
 SEPARATORS REQUIRED. THE EXCEPTION: AN OIL SEPARATOR IS
 NOT REQUIRED IN HYDRAULIC ELEVATOR PITS WHERE AN
 APPROVED ALARM SYSTEM IS INSTALLED. WE WILL NEED THE
 CUT SHEETS AND ALSO NEED TO SEE WHERE THE OIL DETECTOR
 IS TIED INTO AN ALARM SYSTEM.
  
 3) SHEET P2.1
 3A) THERE WERE NO CIVIL PLANS SUBMITTED UNDER THIS
 REVIEW. NOTE #1 INDICATES BACKFLOW REGULATOR TO BE
 PROVIDED BY OTHERS, PLEASE PROVIDE CODE COMPLIANCE WITH
 2010 FBC-P 608.3 DEVICES, APPURTENANCES, APPLIANCES AND
 APPARATUS. ALL DEVICES, APPURTENANCES, APPLIANCES AND
 APPARATUS INTENDED TO SERVE SOME SPECIAL FUNCTION, SUCH
 AS STERILIZATION, DISTILLATION, PROCESSING, COOLING, OR
 STORAGE OF ICE OR FOODS, AND THAT CONNECT TO THE WATER
 SUPPLY SYSTEM, SHALL BE PROVIDED WITH PROTECTION
 AGAINST BACKFLOW AND CONTAMINATION OF THE WATER SUPPLY
 SYSTEM. WATER PUMPS, FILTERS, SOFTENERS, TANKS,
 COMMERCIAL DRINKING WATER DISPENSERS AND ALL OTHER
 APPLIANCES AND DEVICES THAT HANDLE OR TREAT POTABLE
 WATER SHALL BE PROTECTED AGAINST CONTAMINATION.
  
 3B) NOTE NUMBER 6 PROVIDE WATER HAMMER ARESTOR, REF
 GENERAL PLUMBING NOTES, WHERE ? PROVIDE COMPLIANCE WITH
 2010 FBC-P 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S SPECIFICATIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010.
  
 4) PLEASE PROVIDE COMPLIANCE ALL HOSE BIBBS TO HAVE
 BACK FLOW PREVENTORS 2010 FBC-P 608.1 & TABLE 608.1.
  
 5) SHEET P6.2 JANITORS SINK INDICATES THE FAUCET TO
 HAVE THREADED HOSE CONNECTION, PROVIDE COMPLIANCE WITH
 2010 FBC-P 424.6 HOSE-CONNECTED OUTLETS.
 FAUCETS AND FIXTURE FITTINGS WITH HOSE-CONNECTED
 OUTLETS SHALL CONFORM TO ASME A112.18.3M OR CSA B125.
  
 6) SHEET P3.1 THE TEACHER'S LOUNGE SECOND FLOOR SINK
 DOESN'T APPEAR TO HAVE A VENT, THIS SINK WILL NEED TO
 COMPLY WITH FBC-P 907.1 INDIVIDUAL VENT.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER