| Plan Review Notes For Permit 13121076 |
| Permit Number |
13121076 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-01-18 11:44:33 | PLAN DENIED | | | 1) REFER TO SECTION 601.3 EXITS 2010 FBC (M) | | | 2) CAN'T READ MOST OF THE FLEX DUCT SIZE. PLEASE | | | PROVIDE A DUCT SCHEDULE OR MARK THE DUCT SIZE | | | BY THE CFM PER SECTION 107 FBC | | | 3) DETAIL # 2 CONDENSER RACK PAGE M5.2 OF | | | THE PLAN MUST BE 170 MPH PER 103.12 WIND RESISTANCE | | | 2010 FBC (M) | | | 4) DETAIL # 4 PROVIDE WHAT TYPE OF FASTENER AND HOW | | | MANY | | | USED TO TIE RTU TO ROOF CURB. PER SECTION 301.12 WIND | | | RESISTANCE | | | 2010 FBC (M) | | | 5) PROVIDE CFM FOR EXHAUST FANS ON EXHAUST FAN SCHEDULE | | | PER SECTION 107 FBC 2010 | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|