2014-01-18 11:44:33PLAN DENIED
 1) REFER TO SECTION 601.3 EXITS 2010 FBC (M)
 2) CAN'T READ MOST OF THE FLEX DUCT SIZE. PLEASE
 PROVIDE A DUCT SCHEDULE OR MARK THE DUCT SIZE
 BY THE CFM PER SECTION 107 FBC
 3) DETAIL # 2 CONDENSER RACK PAGE M5.2 OF
 THE PLAN MUST BE 170 MPH PER 103.12 WIND RESISTANCE
 2010 FBC (M)
 4) DETAIL # 4 PROVIDE WHAT TYPE OF FASTENER AND HOW
 MANY
 USED TO TIE RTU TO ROOF CURB. PER SECTION 301.12 WIND
 RESISTANCE
 2010 FBC (M)
 5) PROVIDE CFM FOR EXHAUST FANS ON EXHAUST FAN SCHEDULE
 PER SECTION 107 FBC 2010