| 2014-01-03 08:15:19 | BUILDING PLAN REVIEW |
| | PERMIT: 13121076 |
| | ADD: 8151 OKEECHOBEE BLVD |
| | CONT: P & T CONSTRUCTION |
| | TEL: (561)324-8055 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | ARCHITECT: TERCILLA COURTEMANCHE 561-478-4457 |
| | RENE TERCILLA |
| | |
| | STRUCTURAL: RGD CONSULTING ENGINEERS 561-743-0165 |
| | JAMES FARROR |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JAN. 03/2014 |
| | ACTION: DENIED |
| | |
| | 1) LOW EVALUATION ON PERMIT FEES. THE APPLIED VALUE OF |
| | THE BUILDING DECLARED ON THE PERMIT APPLICATION IS |
| | $1,000,000.00. |
| | THE CALCULATED VALUE OF THE BUILDING IS $11,050,000.00 |
| | USING THE AUGUST 2013 ICC EVALUATION TABLES. |
| | |
| | W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. |
| | ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, |
| | AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, |
| | A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| | ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| | APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) FBC* 110.3.9 RESIDENT INSPECTOR. SUBMIT INSPECTOR |
| | RESUME' AND LICENSE DOCUMENTS TO KEN CONRAD, MANAGER OF |
| | THE RESIDENT INSPECTOR PROGRAM. A RESIDENT INSPECTOR |
| | PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO ONE OR |
| | MORE OF THE FOLLOWING: |
| | - BUILDINGS/ADDITIONS OF TYPE I OR II CONSTRUCTION |
| | - ANY MAJOR STRUCTURAL ALTERATIONS |
| | - STRUCTURES IN WHICH THE CONCRETE DESIGN IS BASED ON |
| | COMPRESSIVE STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| | - BUILDINGS OVER 20,000 SQ FT IN AREA |
| | - BUILDINGS OVER 2 STORIES IN HEIGHT- |
| | BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS OF |
| | CONSTRUCTION (TILT WALL). |
| | |
| | PLEASE CONTACT KEN CONRAD AT: |
| | TEL: 561-805-6715 |
| | E-MAIL: [email protected] |
| | |
| | NOTE AN E-MAIL WAS SENT TO JEFFERY CONTE ( 01/04/2014 |
| | 07:16 AM) WITH THE CITY OF WEST PALM BEACH'S GUIDELINES |
| | AND POLICIES FOR PROJECTS CONCERNING SPECIAL INSPECTOR |
| | & RESIDENT INSPECTOR PROGRAM. |
| | |
| | 3A) QUESTIONABLE SOILS REPORT BY A.M. ENGINEERING |
| | PRELIMINARY GEOTECHNICAL REPORT PROJECT NO. PSL219B-1 |
| | DATED JUNE 18,2009. THIS REPORT IS NOT SIGNED NOR |
| | SEALED. |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN |
| | CODE 61G15-23.002 ENGINEERS |
| | |
| | 3B) WITHIN THE FIRST PAGE OF THE SOILS REPORT IT IS |
| | DECLARED THAT THE LAND HAD BEEN STRIPPED AND CLEARED, |
| | DEMUCKED AND BACKFILLED UNDER THIS ADDRESS AND UNDER |
| | 8007, 8101 & 8289 OKEECHOBEE BLVD, THE ADJACENT LOTS |
| | THERE WERE NO PERMITS FOR DEMUCKING AND BACK FILLING. |
| | THE SOILS REPORT ALSO PROCLAIMS THAT REPRESENTATIVES OF |
| | A.M. ENGINEERING AND TESTING PERFORMED DEMUCKING |
| | INSPECTIONS, EARTHWORK TESTING AND VISITED THE SITE |
| | THROUGHOUT THE SITE PREPERATION TO DATE. PLEASE PROVIDE |
| | EITHER A PERMIT NUMBER WHICH WILL ALSO PROVIDE THE BACK |
| | UP DOCUMENTATION REQUIRED OR PRODUCE DOCUMENTS |
| | PROVIDING DOCUMENTATION FOR THE CITY RECORDS. |
| | |
| | 3C) SHEET S1.1 FOUNDATION NOTES AND PARAMETERS, NOTE 1 |
| | & 2 INDICATES THE STRUCTURAL ENGINEER HAS NEVER SEEN |
| | ANY SOILS REPORTS AND HIS FOUNDATION DESIGN IS ONLY AN |
| | ASSUMPTION!!! |
| | |
| | 4) NOTE THIS PROJECT IS LOCATED IN A A-0 FLOOD ZONE. |
| | FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES |
| | SECTION 94-546. PLEASE REVIEW CITY ORDINANCE FOR THE |
| | CITY REQUIREMENTS REQUIRE AN ADDITIONAL 6 INCHES OF |
| | ELEVATION. STRUCTURE IS LOCATED IN AN "A0" FLOOD ZONE. |
| | A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. |
| | |
| | FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| | JULY 31,2015 |
| | |
| | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| | HEIGHT. |
| | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED |
| | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| | ATTENDANT |
| | A/C PADS OR OTHER SLABS FOR GENERATORS ... |
| | |
| | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| | USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. |
| | FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE |
| | NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| | |
| | 5A) THERE ARE NO CIVIL DRAWINGS WITHIN THIS SET OF |
| | PLANS SHEET G1.1 THE OVERALL SITE PLAN DOES NOT |
| | INDICATE ANY DIMENSIONS, A CONCERN IS THE DISTANCE TO |
| | THE EAST PROPERTY LINE, THE PLANS INDICATE A SCALE OF |
| | 1:30 IT APPEARS THE EAST PROPERTY LINE IS AAROUND |
| | 20'-0" ? 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. TABLE 602 |
| | & TABLE 705.8. |
| | |
| | 5B) DIRECTLY WEST OF THIS PROPERTY THERE IS ADDITIONAL |
| | PARKING SPACES, THERE ARE TWO PHASE 3 DESCRIPTION OF |
| | WORK ADDING NEW PARKING SPACES, (1) ADDING 9 SPACES & |
| | (2) ADDING 39 NEW PARKING SPACES, WILL THIS WORK BE |
| | INCLUDED UNDER THIS PERMIT (PROPOSED SITE WORK) OR |
| | UNDER FUTURE PERMITTING? 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 2010 107.2.1.3 ADDITIONAL INFORMATION |
| | IS REQUIRED. 107.3.5.1.1(1) MINIMUM PLAN REVIEW |
| | CRITERIA FOR COMMERCIAL BUILDINGS- SITE WORK. |
| | |
| | 5C) NEITHER G1.1, LS1.1, A1.1 NOR S2.1 PROVIDE WHAT |
| | HEIGHT FINISH FLOOR SLAB ELEVATION WILL BE IN N.G.V.D. |
| | OUR CURRENT FLOOD MAPS ARE IN N.G.V.D. UNKNOWN AS TO |
| | HOW MUCH FILL WILL BE REQUIRED, LIFTS AND |
| | VIBROFLOTATION AS WELL AS DENSITY TEST. |
| | |
| | 6) SHEET LS1.1: |
| | 6A) DEALS WITH THE USE OF A MONUMENTAL STAIR AS PART OF |
| | A MEANS OF EGRESS. THERE ARE SECTIONS OF THE CODE THAT |
| | WILL ALLOW FOR AN UNENCLOSED STAIR. FBC-B 1016.1 DEALS |
| | WITH TRAVEL DISTANCES LEAD FROM THE MOST REMOTE POINT |
| | WITHIN A STORY ALONG HE NATURAL AND UNOBSTRUCTED PATH |
| | OF EGRESS TRAVEL TO AN EXTERIOR EXIT DOOR AT THE LEVEL |
| | OF EXIT DISCHARGE, AN ENTRANCE TO A VERTICAL EXIT |
| | ENCLOSURE, AN EXIT PASSAGEWAY, A HORIZONTAL EXIT, AN |
| | EXTERIOR EXIT STAIRWAY OR AN EXTERIOR EXIT RAMP, SHALL |
| | NOT EXCEED THE DISTANCES GIVEN IN TABLE 1016.1. |
| | EXCEPTIONS: 3. IN OTHER THAN OCCUPANCY GROUPS H AND I, |
| | THE EXIT ACCESS TRAVEL DISTANCE TO A MAXIMUM OF 50 |
| | PERCENT OF THE EXITS IS PERMITTED TO BE MEASURED FROM |
| | THE MOST REMOTE POINT WITHIN A BUILDING TO AN EXIT |
| | USING UNENCLOSED EXIT ACCESS STAIRWAYS OR RAMPS WHEN |
| | CONNECTING A MAXIMUM OF TWO STORIES. THE TWO CONNECTED |
| | STORIES SHALL BE PROVIDED WITH AT LEAST TWO MEANS OF |
| | EGRESS. SUCH INTERCONNECTED STORIES SHALL NOT BE OPEN |
| | TO OTHER STORIES. |
| | |
| | EXITS1020.1 ONCE A GIVEN LEVEL OF EXIT PROTECTION IS |
| | ACHIEVED, SUCH LEVEL OF PROTECTION SHALL NOT BE REDUCED |
| | UNTIL ARRIVAL AT THE EXIT DISCHARGE. |
| | |
| | 1021.3 EXIT CONTINUITY. EXITS SHALL BE CONTINUOUS FROM |
| | THE POINT OF ENTRY INTO THE EXIT TO THE EXIT DISCHARGE. |
| | |
| | WITH THE STAIRWAY # 1 VIEWED AS A EXIT PASSAGEWAY IT |
| | WOULD MEET THE REQUIREMENT OF THE 3RD REQUIRED STAIR |
| | FOR THE OCCUPANT LOAD FOR THE SECOND FLOOR. NUMBER OF |
| | EXITS AND CONTINUITY 1021.1 EXITS FROM STORIES. ALL |
| | SPACES WITHIN EACH STORY SHALL HAVE ACCESS TO THE |
| | MINIMUM NUMBER OF APPROVED INDEPENDENT EXITS AS |
| | SPECIFIED IN TABLE 1021.1 BASED ON THE OCCUPANT LOAD OF |
| | THE STORY. FOR THE PURPOSES OF THIS CHAPTER, OCCUPIED |
| | ROOFS SHALL BE PROVIDED WITH EXITS AS REQUIRED FOR |
| | STORIES. |
| | EXCEPTIONS: 3. EXIT ACCESS STAIRWAYS AND RAMPS THAT |
| | COMPLY WITH EXCEPTION 3 OR 4 OF SECTION 1016.1 SHALL BE |
| | PERMITTED TO PROVIDE THE MINIMUM NUMBER OF APPROVED |
| | INDEPENDENT EXITS REQUIRED BY TABLE 1021.1 ON EACH |
| | STORY. |
| | |
| | WHAT I BELIEVE THE DESIGNER OF RECORD IS TRYING TO |
| | ACCOMPLISH IS EITHER USING STAIRWELL # 1 AS EITHER A |
| | EXIT PASSAGEWAY ( WOULD NEED TO MEET THE REQUIREMENTS |
| | OF FBC-B 1023 OR A HORIZONTAL EXIT. IN EITHER CASE THE |
| | RESTROOMS LOCATED ON THE FIRST FLOOR IN THE STAIRWELL |
| | WOULD NEED TO BE REMOVED FROM THIS AREA. |
| | |
| | ACCORDING TO THE DEFINITION OF MEANS OF EGRESS IT IS |
| | CONTINUOUS PATH WITH AN EXIT ACCESS, EXIT AND EXIT |
| | DISCHARGE. TO CLASSIFY STAIRWELL # 1 AS A HORIZONTAL |
| | EXIT WOULD BE MORE RESTRICTIVE, FBC-B 1025.2 SEPERATION |
| | REQUIRES 2 HR SEPERATION SEE OTHER REQUIREMENTS UNDER |
| | FBC-B 1025. |
| | |
| | 6B) PLEASE BREAK DOWN THE OCCUPANT LOADS FOR EACH FLOOR |
| | , TOTAL OCCUPANT LOAD NOT PROVIDED. FBC-B 1004.1 & |
| | TABLE 1004.1. |
| | |
| | 6C) PLEASE PROVIDE WHAT USE THE PANTRY WILL BE USED |
| | FOR? DEFINITION: A ROOM OR CLOSET USED FOR STORAGE (AS |
| | OF PROVISIONS) OR FROM WHICH FOOD IS BROUGHT TO THE |
| | TABLE. 1014.2 EXCEP (4) EGRESS SHALL NOT PASS THROUGH |
| | KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES USED FOR |
| | SIMILAR PURPOSES. |
| | |
| | 6D) WHAT IS THE 2 AREAS ADJACENT TO THE PANTRY ROOM |
| | 106B MARKED WITH A X OCCUPANCY UNKNOWN? 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 6E) STORAGE CLOSET 104B, MUSIC LAB STORAGE CLOSET 11A & |
| | SRT LAB STORAGE CLOSET NOT OCCUPANT LOADS WERE PROVIDED |
| | FOR THESE STORAGE AREAS. FBC-B 1004.1 & TABLE 1004.1. |
| | |
| | 7) LS 1.1 & LS 2.1 INDICATE 1 HOUR RATED WALLS AT STAIR |
| | # 1 AS WELL AS THE ELEVATOR SHAFT SHEET A1.4 DETAIL # 3 |
| | INDICATES FIRE CAULK ALL BAR JOIST OR BEAMS |
| | INTERSECTIONS WITH |
| | GYPSUM WALL BOARD. PLEASE COMPLY WITH FBC-B 714.1 |
| | JOINTS INSTALLED IN OR BETWEEN FIRE-RESISTANCE-RATED |
| | WALLS, FLOOR OR FLOOR/CEILING ASSEMBLIES AND ROOFS OR |
| | ROOF/CEILING ASSEMBLIES SHALL BE PROTECTED BY AN |
| | APPROVED FIRE-RESISTANT JOINT SYSTEM DESIGNED TO RESIST |
| | THE PASSAGE OF FIRE FOR A TIME PERIOD NOT LESS THAN THE |
| | REQUIRED FIRE-RESISTANCE RATING OF THE WALL, FLOOR OR |
| | ROOF IN OR BETWEEN WHICH IT IS INSTALLED. |
| | FIRE-RESISTANT JOINT SYSTEMS SHALL BE TESTED IN |
| | ACCORDANCE WITH SECTION 714.3. THE VOID CREATED AT THE |
| | INTERSECTION OF A FLOOR/CEILING ASSEMBLY AND AN |
| | EXTERIOR CURTAIN WALL ASSEMBLY SHALL BE PROTECTED IN |
| | ACCORDANCE WITH SECTION 714.4. |
| | |
| | 8) SHEET A5.1 INDICATES THE USE OF 2 INCH RIGID |
| | INSULATION, THE ENERGY CALCULATIONS INDICATE THIS TO BE |
| | POLYISOCYANURATE OR FOAM PLASTIC, AND THE M SHEETS SHOW |
| | PLENUM RETURN AIR, PLEASE PROVIDE COMPLIANCE WITH FBC-B |
| | 2603.4 THERMAL BARRIER, 2603.4.1.6 IGNITION BARRIER, |
| | FBC-MECHANICAL 602.2.1.5 & M 602.2.1.5.1 SEPERATION |
| | REQUIRED. |
| | |
| | 9) THE ARCHITECTURAL SHEETS DO NOT PROVIDE WHERE THE |
| | ELEVATOR SHAFT ENDS. FBC-B 3002.1 HOISTWAY ENCLOSURE |
| | PROTECTION. ELEVATOR, DUMBWAITER AND OTHER HOISTWAY |
| | ENCLOSURES SHALL BE SHAFT ENCLOSURES COMPLYING WITH |
| | SECTION 708. |
| | |
| | FBC-B 708.12 ENCLOSURE AT THE TOP. |
| | A SHAFT ENCLOSURE THAT DOES NOT EXTEND TO THE UNDERSIDE |
| | OF THE ROOF SHEATHING, DECK OR SLAB OF THE BUILDING |
| | SHALL BE ENCLOSED AT THE TOP WITH CONSTRUCTION OF THE |
| | SAME FIRE-RESISTANCE RATING AS THE TOPMOST FLOOR |
| | PENETRATED BY THE SHAFT, BUT NOT LESS THAN THE |
| | FIRE-RESISTANCE RATING REQUIRED FOR THE SHAFT |
| | ENCLOSURE. |
| | |
| | 10) SHEET S1.2: |
| | 10A) THE PLANS INDICATE THE 2ND FLOOR LIVE LOADS FOR |
| | CLASS ROOMS AND CORRIDORS BUT NOT THE STAIRS 2010 FBC-B |
| | TABLE 1607.1. |
| | |
| | 10B) THE WIND DESIGN CRITERIA IS PROVIDED IN VULT AS |
| | PER 2010 FBC, ASCE 7-10, PLEASE ALSO PROVIDE VASD SINCE |
| | ALL PRODUCT TESTING IS IN VASD. FBC-B 1609.1.5. |
| | |
| | 10C) ROOF PRESSURES PROVIDED ARE FOR FLAT ROOFS NO |
| | DESIGN CRITERIA IS PROVIDED FOR THE SLOPED ROOFS |
| | 7DEGREES TO 27 DEGREES. |
| | |
| | 11) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 12) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 13) 43.2.2 PLAYGROUNDS AND EQUIPMENT. |
| | PLAYGROUNDS AND EQUIPMENT SHALL BE SAFE, STRUCTURALLY |
| | SOUND, VERMINPROOF, AND SHALL NOT HAVE JAGGED OR SHARP |
| | PROJECTIONS. PLAYGROUND EQUIPMENT SHALL BE ANCHORED TO |
| | SUITABLE FOUNDATIONS TO PREVENT TOPPLING OR |
| | DISLODGEMENT. CUSHIONING MATERIALS SUCH AS MATS, WOOD |
| | CHIPS, OR SAND SHALL BE USED UNDER CLIMBING EQUIPMENT, |
| | SLIDES, AND SWINGS. |
| | |
| | 14) 443.2.3 OUTDOOR WASTE CONTAINERS. A SMOOTH |
| | NONABSORBENT SURFACE SHALL BE PROVIDED FOR OUTDOOR |
| | WASTE CONTAINERS. |
| | |
| | 15) 443.3.2 GLARE FROM NATURAL LIGHT. SOURCES OF |
| | NATURAL LIGHT IN INSTRUCTIONAL SPACES SHALL BE GLAZED |
| | WITH GLARE REDUCING MATERIALS OR SHALL BE SHIELDED TO |
| | PREVENT GLARE THAT CAN INTERFERE WITH SEEING TASK |
| | WITHIN THE INSTRUCTIONAL SPACE. |
| | |
| | 16) 443.3.3 AUTOMATED EXTERNAL DEFIBRILLATOR. AUTOMATED |
| | EXTERNAL DEFIBRILLATORS SHALL BE PROVIDED IN PUBLIC |
| | EDUCATIONAL FACILITIES THAT ARE A MEMBER OF THE FLORIDA |
| | HIGH SCHOOL ATHLETIC ASSOCIATION. |
| | |
| | 17) 443.3.4 DIAPER CHANGING STATIONS. A DIAPER CHANGING |
| | STATION SHALL BE LOCATED IN OR ADJACENT TO ANY |
| | CLASSROOM WHERE CHILDREN WEARING DIAPERS ARE IN |
| | ATTENDANCE. A HAND WASHING LAVATORY SHALL BE PROVIDED |
| | WITHIN THE CHANGING STATION AREA. ACCESS SHALL BE |
| | PROVIDED TO THE LAVATORY WITHOUT OPENING DOORS OR |
| | TOUCHING A HANDLE. |
| | |
| | 18) 443.3.6.5 CHEMICAL STORAGE. |
| | ROOMS USED FOR THE STORAGE, HANDLING, AND DISPOSAL OF |
| | CHEMICALS USED IN SCHOOL, COLLEGE, AND UNIVERSITY |
| | LABORATORIES SHALL BE VENTED TO THE EXTERIOR. THE |
| | VENTILATION SYSTEM SHALL NOT BE CONNECTED TO THE |
| | AIR-CONDITIONING RETURN AIR SYSTEM, AND THE ROOMS SHALL |
| | BE KEPT AT MODERATE TEMPERATURES. CHEMICAL STORAGE |
| | CABINETS, WHEN VENTED TO THE EXTERIOR, SHALL BE |
| | MECHANICALLY VENTED IN ACCORDANCE WITH NFPA 30 AND NFPA |
| | 91. |
| | |
| | 19) 443.3.7.1 ILLUMINATION LEVEL IN |
| | CLASSROOMS/INSTRUCTIONAL SPACES. |
| | ILLUMINATION AT THE NORMAL TASK LEVEL FOR THE TYPE OF |
| | CLASSROOM/INSTRUCTION SPACE SHALL BE A MINIMUM OF FORTY |
| | (40) FOOT-CANDLES (400 LUX). |
| | |
| | 443.3.7.2 ILLUMINATION UNIFORMITY IN |
| | CLASSROOMS/INSTRUCTION SPACES. |
| | LUMINARIES SHALL HAVE A CEILING ARRANGEMENT OR |
| | POSITIONED AROUND THE WALLS SUCH THAT A UNIFORMED |
| | ILLUMINATION LEVEL, WITHIN TEN (10) FOOT-CANDLES (100 |
| | LUX), IS MAINTAINED AT THE STUDENTS REQUIRED NORMAL |
| | TASK LEVEL FOR THE TYPE OF CLASSROOM/INSTRUCTION SPACE. |
| | |
| | 443.3.7.3 BRIGHTNESS RATIO IN CLASSROOMS/INSTRUCTIONAL |
| | SPACES. |
| | THE BRIGHTNESS RATIO BETWEEN THE STUDENT TASK LEVEL AND |
| | THE INSTRUCTION AREA OR AREAS OR VISUAL DISPLAY |
| | LOCATION SHALL BE ONE(1) TO FIVE(5) OR LESS. |
| | |
| | 443.3.7.4 ILLUMINATION FAILURE OF GENERAL AND MEANS OF |
| | EGRESS LUMINARIES. |
| | ILLUMINATION SYSTEMS SHALL BE DESIGNED AND MAINTAINED |
| | SO THAT THE FAILURE OF ANY SINGLE LIGHTING UNIT, SUCH |
| | AS AN ELECTRIC LUMINARY, DOES NOT LEAVE ANY OCCUPIED |
| | SPACE OR MEANS OF EGRESS IN THE DARK. (SEE FLORIDA |
| | BUILDING CODE, BUILDING SECTION 1006 FOR ADDITIONAL |
| | MEANS OF EGRESS REQUIREMENTS.) |
| | |
| | 443.3.7.5 GLARE ELIMINATION. |
| | ILLUMINATION OF PERMANENTLY INSTALLED MARKERBOARDS, |
| | CHALKBOARDS, AND OTHER INSTRUCTION AIDS SHALL BE |
| | DESIGNED TO ELIMINATE GLARE AND SHADOWS. |
| | |
| | 20) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |