Plan Review Notes
Plan Review Notes For Permit 13121071
Permit Number 13121071
Review Stop B
Sequence Number 1
Notes
Date Text
2014-01-02 11:28:53BUILDING PLAN REVIEW
 PERMIT: 13121071
 ADD: 501 FERN ST
 CONT: EDS ISLAND TIME SERVICES
 TEL: (561)541-00041ST
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURSDAY JAN 02/ 2014
 ACTION: DENIED
  
 1) THERE IS A OPEN PERMIT FOR TENANT SPACE B2 (PERMIT #
 13080940) WHICH SHOWS A FRAMING DETAIL FOR A NEW ROOF
 HATCH.
 THE LOCATION OF THE ROOF HATCH IS SHOWN ON THIS PLAN,
 BUT THERE ARE UNKNOWNS,:
  
 1A) WHAT IS THE DIFFERENCE BETWEEN ROOF TOPS FOR TENANT
 B2 AND TENANT FOR TENANT TO BE LOCATED IN SECTION "A".
 IS THE ROOF TO TENANT B2 HIGHER OR LOWER THAT TANANT A?
 IS THERE A PARAPET BETWEEN THE TWO UNITS, IS THE
 LOCATION OF THE ROOF HATCH IN A ROOF ZONE 2? WHAT IS
 THE ROOF PRESSURES FOR THIS LOCATION FOR A "C" EXPOSURE
 AND HEIGHT ADJUSTMENT FACOR? 2010 FBC-B 1609.6.
  
 1B) PERMIT 13080940 SHEET A.4 EAST ELEVSATION IT
 APPEARS THE B TENANCY ROOF IS HIGHER AND WILL NEED TO
 COMPLY WITH:
 2010 FBC-B 1013.6 ROOF ACCESS.
 GUARDS SHALL BE PROVIDED WHERE THE ROOF HATCH OPENING
 IS LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR
 OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN
 SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE
 FLOOR, ROOF OR GRADE BELOW. THE GUARD SHALL BE
 CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21
 INCHES (533 MM) IN DIAMETER.
  
 1C) 2010 FBC-B1013.5 MECHANICAL EQUIPMENT.
 GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT,
 FANS, ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT
 REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF
 A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH
 EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD
 SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A
 SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL
 EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND EACH END
 OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT.
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  