| 2014-01-02 11:28:53 | BUILDING PLAN REVIEW |
| | PERMIT: 13121071 |
| | ADD: 501 FERN ST |
| | CONT: EDS ISLAND TIME SERVICES |
| | TEL: (561)541-00041ST |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURSDAY JAN 02/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) THERE IS A OPEN PERMIT FOR TENANT SPACE B2 (PERMIT # |
| | 13080940) WHICH SHOWS A FRAMING DETAIL FOR A NEW ROOF |
| | HATCH. |
| | THE LOCATION OF THE ROOF HATCH IS SHOWN ON THIS PLAN, |
| | BUT THERE ARE UNKNOWNS,: |
| | |
| | 1A) WHAT IS THE DIFFERENCE BETWEEN ROOF TOPS FOR TENANT |
| | B2 AND TENANT FOR TENANT TO BE LOCATED IN SECTION "A". |
| | IS THE ROOF TO TENANT B2 HIGHER OR LOWER THAT TANANT A? |
| | IS THERE A PARAPET BETWEEN THE TWO UNITS, IS THE |
| | LOCATION OF THE ROOF HATCH IN A ROOF ZONE 2? WHAT IS |
| | THE ROOF PRESSURES FOR THIS LOCATION FOR A "C" EXPOSURE |
| | AND HEIGHT ADJUSTMENT FACOR? 2010 FBC-B 1609.6. |
| | |
| | 1B) PERMIT 13080940 SHEET A.4 EAST ELEVSATION IT |
| | APPEARS THE B TENANCY ROOF IS HIGHER AND WILL NEED TO |
| | COMPLY WITH: |
| | 2010 FBC-B 1013.6 ROOF ACCESS. |
| | GUARDS SHALL BE PROVIDED WHERE THE ROOF HATCH OPENING |
| | IS LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR |
| | OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN |
| | SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE |
| | FLOOR, ROOF OR GRADE BELOW. THE GUARD SHALL BE |
| | CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21 |
| | INCHES (533 MM) IN DIAMETER. |
| | |
| | 1C) 2010 FBC-B1013.5 MECHANICAL EQUIPMENT. |
| | GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT, |
| | FANS, ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT |
| | REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF |
| | A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH |
| | EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762 |
| | MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD |
| | SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A |
| | SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL |
| | EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND EACH END |
| | OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT. |
| | |
| | 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |