2014-01-10 16:44:41BUILDING PLAN REVIEW
 PERMIT: 13121049
 ADD: 10130 NORTHLAKES BLVD # 218
 CONT: VENTURA ARCHITECTURE DEVELOPMENT
 TEL: (954) 423-1362
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1STREVIEW
 DATE: FRIDAY JAN.10/ 2014
 ACTION: PROVISO APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) THE PRODUCT APPROVAL SUBMITTED FOR THE GLAZED
 STOREFRONT NOA 11-1207.07 TRULITE REGISTER FG-4500/ 450
 EZ IS A NON-IMPACT GLAZED SYSTEM. PLEASE PROVIDE
 COMPLIANCE WITH 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING STORM
 SHUTTERS. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(E) SHUTTER.
  
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.4.
  
 FL BLD CODE 2004 SECTION 106.3.3, 1609.1.4, 1714.5.1 &
 EXIST BUILD CODE 507.3. PROCEDURES: 1(B) A COMPLETE
 INSTALLATION SCHEDULE SUMMARIZING & IDENTIFYING OPENING
 SIZES, STORY HEIGHTS, UNIT MARK NUMBERS, UNIT
 SPANS/WIDTHS, UNIT BAR REINFORCING REQUIREMENTS, WALL
 PRESSURE ZONES, SLAT TYPES, ETC.
  
 2) SHEET A2 SECTIONS 1,2 & 3 2010 FBC-ENERGY 502.2.1.2
 CEILING INSULATION. INSULATION INSTALLED ON A SUSPENDED
 CEILING WITH REMOVABLE CEILING TILES SHALL NOT BE
 CONSIDERED PART OF THE MINIMUM THERMAL RESISTANCE OF
 THE ROOF INSULATION UNLESS THE ROOF/CEILING CAVITY IS
 SEALED FROM THE EXTERIOR ENVIRONMENT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  