| 2014-02-23 10:48:21 | BUILDING PLAN REVIEW |
| | PERMIT:13121042 |
| | ADD: 600 OKEECHOBEE BLVD. |
| | EARTHWORK & FOUNDATION PERMIT |
| | P. B. CONVENTION CENTER HILTON HOTEL |
| | CONT: COASTAL CONSTRUCTION |
| | E;MAIL : NO CONTACT INFORMATION GIVEN |
| | TEL: (561) 630-3770 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: SUN. FEB. 23/ 2014 |
| | ACTION: DENIED |
| | |
| | COASTAL CONSTRUCTION: THE TELEPHONE NUMBER WE ON FILE |
| | FOR BUSINESS IS NON-WORKING NUMBER. WE ALSO DO NOT HAVE |
| | A E-MAIL ADDRESS TO BE ABLE TO SEND REQUIRED FORMS AND |
| | INFORMATION DURING THE LIFR OF THIS PROJECT. |
| | |
| | NOTE: THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA |
| | AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. |
| | |
| | 1A)COMPLIED. |
| | WRITTEN THRESHOLD INSPECTION PLAN. S-0.02 109.3.6.1 THE |
| | ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO |
| | PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING |
| | PURSUANT TO A WRITTEN STRUCTURAL INSPECTION PLAN |
| | PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 1B) COMPLIED. |
| | THRESHOLD BLDG, REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| | |
| | 1C) 2ND REQUEST, THRESHOLD INSPECTOR: WPB AMENDMENT |
| | 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS |
| | REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE |
| | MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT KEN |
| | CONRAD MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT |
| | (561)805-6666 FOR FURTHER INFORMATION BEFORE THE PERMIT |
| | MAY BE ISSUED. |
| | THRESHOLD INSPECTORS ARE REQUIRED TO HAVE THRESHOLD |
| | INSPECTOR AGREEMENTS SIGNED BY ALL PARTIES AND INTO |
| | THIS OFFICE REVIEWED AND APPROVED BEFORE A PERMIT CAN |
| | BE ISSUED. |
| | |
| | 1C)(1) 2ND REQUEST. |
| | THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY |
| | FOR THIS TYPE OF CONSTRUCTION. |
| | THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN |
| | CONRAD: [email protected], TEL: 561-805-6715 |
| | |
| | 1C)(2) COMPLIED. |
| | FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' OF |
| | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME' |
| | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| | REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, AN |
| | INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 1D) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |