| 2014-01-26 09:10:39 | PLUMBING PLAN REVIEW |
| | PERMIT:13121042 |
| | ADD: 600 OKEECHOBEE BLVD. |
| | EARTHWORK & FOUNDATION PERMIT |
| | P. B. CONVENTION CENTER HILTON HOTEL |
| | CONT: COASTAL CONSTRUCTION |
| | E;MAIL : NO CONTACT INFORMATION GIVEN |
| | TEL: (561) 630-3770 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: SAT.25/ SUN 26 JAN./ 2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET PF-1.00: |
| | 1A)(1) THE MENS & WOMENS RESROOMS B009 & (B???- WOMENS |
| | NOT LABELED) SHOW THE 4 INCH SANITARY, NOTE NUMBER 4 |
| | INDICATES FROM RESTROOMS, THE NOTE DOESN'T INDICATE IF |
| | THE WATER CLOSETS ARE TO BE WALL HUNG WITH THE SANITARY |
| | LINE ABOVE THE SLAB. THE SAME ISSUE WITH THE WASTE AND |
| | VENTING FOR THE LAVS THE PLANS DO NOT SHOW A WALL IT IS |
| | BEING ASSUMED THE 4 INCH SANITARY IS ABOVE THE FLOOR |
| | UNTIL AFTER THE LAVATORIES THEN STARTS TO RUN BENEATH |
| | THE SLAB.PLEASE PROVIDE ADDITIONAL INFORMATION, |
| | 107.2.1.3 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| | EDITION. A ISOMETRIC DRAWING WOULD GREATLY HELP. |
| | 1A)(2) NOT REQUIRED. |
| | |
| | 1B) IN THE DOMESTIC PUMP ROOM (B002) AND FIRE PUMP ROOM |
| | (B003) THE PLANS INDICATE THE USE OF 3 INCH FLOOR |
| | DRAINS THE KEY NOTES DO NOT INDICATE THE INSTALATION OF |
| | TRAP PRIMERS AS REQUIRED BY 2010 FBC-P 1002.4. WHERE A |
| | TRAP SEAL IS SUBJECT TO LOSS BY EVAPORATION, A TRAP |
| | SEAL PRIMER VALVE SHALL BE INSTALLED. TRAP SEAL PRIMER |
| | VALVES SHALL CONNECT TO THE TRAP AT A POINT ABOVE THE |
| | LEVEL OF THE TRAP SEAL. A TRAP SEAL PRIMER VALVE SHALL |
| | CONFORM TO ASSE 1018 OR ASSE 1044. |
| | |
| | 1C) ACTIVE LINEN STORAGE (B006D) SHOW WHAT APPEARS TO |
| | BE 3 WASHING MACHINES AND A 3 INCH FLOOR DRAIN IN FRONT |
| | OF THE CLOTHES WASHING MACHINES. PLEASE CLARIFY |
| | IF THIS IS TO BE AN EMERGENCY FLOOR DRAIN REQUIRING A |
| | TRAP SEAL FBC-P 1002.4 OR IF THE INTENT TO HAVE EACH OF |
| | THE AUTOMATIC CLOTHES WASHERS TO HAVE THEIR OWN |
| | STNDPIPE OR TO DRAIN INTO A TRENCH DRAIN OR WASTE |
| | RECEPTOR? SEE FBC-P 406.3. |
| | 1D) NOTE NUMBER ONE INDICATES THE USE OF A SANITARY |
| | LIFT STATION. THERE ARE NO NOTES ON THIS SHEET NOR ON |
| | THE FOUNDATION PLANS ABOUT THE REQUIRED SIZE OF THE |
| | SUMP PIT, NOR AT WHAT ELEVATION THE 4 INCH SANITARY |
| | LINE WILL ENTER THE PIT PLEASE PROVIDE COMPLIANCE WITH |
| | FBC-P 712,3,2, THE SIZE LISTED IN THE CODE IS MINIMUM |
| | SIZE, DEPENDING ON THE DEMAND AND SIZING OF THE SUMP OR |
| | EJECTOR THIS SIZE WILL GREATLY DIFFER. |
| | |
| | 1E) SANITARY LIFT STATION NOTE # 1 PLEASE PROVIDE THE |
| | CAPACITY FOR THE SEWAGE PUMP OR SEWAGE EJECTOR FOR THE |
| | 4 INCH SANITARY LINE. THE FBC-P TABLE 712.4.2 TABLE |
| | GOES UP TO 46 GPM. 712.4.2 CAPACITY. A SEWAGE PUMP OR |
| | SEWAGE EJECTOR SHALL HAVE THE CAPACITY AND HEAD FOR THE |
| | APPLICATION REQUIREMENTS. PUMPS OR EJECTORS THAT |
| | RECEIVE THE DISCHARGE OF WATER CLOSETS SHALL BE CAPABLE |
| | OF HANDLING SPHERICAL SOLIDS WITH A DIAMETER OF UP TO |
| | AND INCLUDING 2 INCHES (51 MM). OTHER PUMPS OR EJECTORS |
| | SHALL BE CAPABLE OF HANDLING SPHERICAL SOLIDS WITH A |
| | DIAMETER OF UP TO AND INCLUDING 1 INCH (25.4 MM). THE |
| | MINIMUM CAPACITY OF A PUMP OR EJECTOR BASED ON THE |
| | DIAMETER OF THE DISCHARGE PIPE SHALL BE IN ACCORDANCE |
| | WITH TABLE 712.4.2. |
| | |
| | 1F) 2010 FBC-P 712.3.5 EJECTOR CONNECTION TO THE |
| | DRAINAGE SYSTEM. |
| | PUMPS CONNECTED TO THE DRAINAGE SYSTEM SHALL CONNECT TO |
| | THE BUILDING SEWER OR SHALL CONNECT TO A WYE FITTING IN |
| | THE BUILDING DRAIN A MINIMUM OF 10 FEET (3048 MM) FROM |
| | THE BASE OF ANY SOIL STACK, WASTE STACK OR FIXTURE |
| | DRAIN. WHERE THE DISCHARGE LINE CONNECTS INTO |
| | HORIZONTAL DRAINAGE PIPING, THE CONNECTOR SHALL BE MADE |
| | THROUGH A WYE FITTING INTO THE TOP OF THE DRAINAGE |
| | PIPING. |
| | |
| | 1G)(1) SERVICE ELEVATOR (B016) & ELEVATOR MACHINE ROOM |
| | (B001) THE PLANS DO NOT INDICATE THE TYPE OF ELEVATOR |
| | TO BE INSTALLED IF HYDROLIC ELEVATORS ARE TO BE |
| | INSTALLED COMPLIANCE WIH 2010 FBC-B 3004.4 PLUMBING AND |
| | MECHANICAL SYSTEMS. PLUMBING AND MECHANICAL SYSTEMS |
| | SHALL NOT BE LOCATED IN AN ELEVATOR SHAFT. |
| | EXCEPTION: FLOOR DRAINS, SUMPS AND SUMP PUMPS SHALL BE |
| | PERMITTED AT THE BASE OF THE SHAFT PROVIDED THEY ARE |
| | INDIRECTLY CONNECTED TO THE PLUMBING SYSTEM. |
| | |
| | 1G)(2) IF A SUMP & SUMP PIT IS REQUIRED THE DESIGNER |
| | WILL ALSO NEED TO COMPLY WITH FBC-P 1003.4 OIL |
| | SEPARATOR OR PROVIDE DOCUMENTATION FOR A OIL & WATER |
| | SENSING DEVICE WHERE AN APPROVED ALARM SYSTEM IS |
| | INSTALLED. |
| | |
| | 1H)(1) THE PLANS INDICATE THIS FLOOR TO BE A BUSINESS |
| | AND HOUSEKEEPING AREA, AND A ASSOCIATES CAFETERIA, THE |
| | PLANS DO NOT DECLARE THE TYPE OF OCCUPANCIES NOR |
| | THE OCCUPANCY LOAD, PLAN REVIEW CAN NOT DETERMINE CODE |
| | COMPLIANCE WITH 2010 FBC-P TABLE 403.1 FOR WATER |
| | CLOSETS AND LAVATORIES. |
| | |
| | 1H)(2) THE PLANS ARE MISSING DRINKING FOUNTAINS |
| | INACCORDANCE WITH FBC-P TABLE 403.3 NOTE THE 2010 FL |
| | ACCESSIBILITY CODE SCOPING REQUIREMENT 211 AT A MINIMUM |
| | WILL REQUIRE A HIGH / LOW FIXTURE. |
| | 1H)(3) THE SERVICE AND STORAGE AREA WILL ALSO NEED TO |
| | COMPLY WITH 2010 FBC-P TABLE 403.3 FOR A MOP/ SERVICE |
| | SINK. |
| | |
| | 2) SHEET PF 1.01: |
| | |
| | 2A) THIS COMMENT WILL SERVE FOR ALL SHEETS THAT DEAL |
| | WITH ROOF RAIN LETTERS. 2010 FBC-P 1101.3 PROHIBITED |
| | DRAINAGE. STORM WATER SHALL NOT BE DRAINED INTO SEWERS |
| | INTENDED FOR SEWAGE ONLY. |
| | |
| | 2B) THIS COMMENT WILL SERVE FOR ALL SHEETS THAT DEAL |
| | WITH ROOF RAIN LETTERS. ROOF DRAINAGE IS SIZED FROM THE |
| | ROOF TOP AREA INCLUDING 1/2 OF ALL VERTICAL SURFACES. |
| | UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES, |
| | DESIGN AND INSTALLATION OF ROOF DRAINAGE SYSTEMS SHALL |
| | COMPLY WITH SECTION 1503 AND THE FLORIDA BUILDING CODE, |
| | PLUMBING, CHAPTER 11. SIZING OF THE VERTICAL CONDUCTORS |
| | AND LEADERS, BUILDING STORM DRAINS, BUILDING STORM |
| | SEWERS, AND ANY HORIZONTAL BRANCHES OF SUCH DRAINS OR |
| | SEWERS SHALL BE BASED ON THE 100-YEAR HOURLY RAINFALL |
| | RATE INDICATED IN FIGURE 1106.1 OR ON OTHER RAINFALL |
| | RATES DETERMINED FROM APPROVED LOCAL WEATHER DATA. WEST |
| | PALM BEACH'S 100-YEAR, 1-HOUR RAINFALL IS 4.5 (INCHES). |
| | PLEASE SIZE ACCORDINGLY PROVIDE ROOF TOP CALCULATIONS |
| | AND CAPACITY FOR THE VERTICAL CONNECTORS & HORIZONTAL |
| | STORM DRAINAGE PIPING TABLES 1106.2(1) & TABLE 1106.2.3 |
| | . |
| | |
| | 2C) THE STORAGE ROOM 126 INDICATES A 6 INCH SANITARY |
| | BACKWASH LINE FROM THE POOL EQUIPMENT ROOM AT FLOOR |
| | BELOW, TO SPILL INDIRECTLY TO A 6 INCH HUB DRAIN SHOWN |
| | AS A SANITARY LINE. THE CITY MUNICIPLE CODE OF WEST |
| | PALM BEACH SECTION 90-126 PROHIBITATION AND LIMITATION |
| | OF DISCHARGE (5) SWIMMING POOL AS WELL AS AIR |
| | CONDITIONING CONDENSATE FROM ENTERING THE SANITARY |
| | SEWER SYSTEM. |
| | |
| | 2D) THE RESTROOMS 124 & 125 THAT SERVICE THE POOL AREA |
| | ARE ALSO MISSING FLOOR DRAINS. FBC-P 403.6.3 SANITARY |
| | FACILITY FLOORS. FLOORS OF SANITARY FACILITIES SHALL BE |
| | CONSTRUCTED OF CONCRETE OR OTHER NONABSORBENT |
| | MATERIALS, SHALL HAVE A SMOOTH, SLIP-RESISTANT FINISH, |
| | AND SHALL SLOPE TO FLOOR DRAINS. CARPETS, DUCKBOARDS |
| | AND FOOT-BATHS ARE PROHIBITED. THE INTERSECTION BETWEEN |
| | THE FLOOR AND WALLS SHALL BE COVED WHERE EITHER FLOOR |
| | OR WALL IS NOT MADE OF WATERPROOF MATERIALS SUCH AS |
| | TILE OR VINYL. |
| | |
| | 2E) THE TOTAL POOL & POOL DECK (A4 OCCUPANCY) ARE NOT |
| | SHOWN NOR IS THE OCUPANT LOAD COUNT SIZING OF THE |
| | RESTROOMS CAN NOT BE ESTABLISHED TO CODE COMPLIANCE |
| | WITH 2010 FBC-P TABLE 403.1. |
| | |
| | 2F) COMPLIANCE WITH FBC-P TABLE (A4 OCCUPANCY) 403.1 |
| | FOR DRINKING FOUNTAINS HAS NOT BEEN COMPLIED WITH, NOT |
| | SHOWN ON SANITARY. |
| | |
| | 2G) COMPLIANCE WITH FBC-P TABLE (A4) 403.1 FOR SERVICE |
| | SINK/ MOP SINK HAS NOT BEEN COMPLIED WITH, NOT SHOWN ON |
| | SANITARY. |
| | |
| | 3) SHEET PF1.02 THIS COMMENT WILL SERVE FOR ALL SHEETS |
| | THAT DEAL WITH ROOF RAIN LETTERS. ROOF DRAINAGE IS |
| | SIZED FROM THE ROOF TOP AREA INCLUDING 1/2 OF ALL |
| | VERTICAL SURFACES. UNLESS ROOFS ARE SLOPED TO DRAIN |
| | OVER ROOF EDGES, DESIGN AND INSTALLATION OF ROOF |
| | DRAINAGE SYSTEMS SHALL COMPLY WITH SECTION 1503 AND THE |
| | FLORIDA BUILDING CODE, PLUMBING, CHAPTER 11. SIZING OF |
| | THE VERTICAL CONDUCTORS AND LEADERS, BUILDING STORM |
| | DRAINS, BUILDING STORM SEWERS, AND ANY HORIZONTAL |
| | BRANCHES OF SUCH DRAINS OR SEWERS SHALL BE BASED ON THE |
| | 100-YEAR HOURLY RAINFALL RATE INDICATED IN FIGURE |
| | 1106.1 OR ON OTHER RAINFALL RATES DETERMINED FROM |
| | APPROVED LOCAL WEATHER DATA. WEST PALM BEACH'S |
| | 100-YEAR, 1-HOUR RAINFALL IS 4.5 (INCHES). PLEASE SIZE |
| | ACCORDINGLY PROVIDE ROOF TOP CALCULATIONS AND CAPACITY |
| | FOR THE VERTICAL CONNECTORS & HORIZONTAL STORM DRAINAGE |
| | PIPING TABLES 1106.2(1) & TABLE 1106.2.3 . |
| | |
| | 4) SHEET PF 1.03 |
| | 4A) PLEASE IDENTFY ALL PLUMBING FIXTURES & EQUIPMENT |
| | WITH THE KITCHEN AND BAR AREA TO KNOW WHAT THE |
| | REQUIREMENTS ARE FOR BOTH THE INDIRECT WASTE |
| | REQUIREMENTS FOUND IN 802 AND THE REQUIREMENTS FOR |
| | SIZING REQUIREMENTS FOUND FOR SIZING OF THE GREASE |
| | INTERCEPTOR IN SECTION 1003.3.4 & TABLE 1003.5.1, |
| | INCLUDE THE LOADING FACTOR. PLEASE PROVIDE METHOD FOR |
| | SIZING. |
| | |
| | 4B) THE PLANS INDICATE IN THE KITCHEN 2 FLOOR DRAINS |
| | AND A 4 INCH FLOOR SINK BUT IT IS NOT CLEAR AS IF THERE |
| | IS MORE THAN THE 3 COMPATMENT SINK EMPTYING INTO THE |
| | FLOOR SINK. THERE APPEARS TO BE AT LEAST ONE HAND SINK |
| | WITH NO WASTE CONECTED AND THE PLANS DO NOT INDICATE |
| | ANY AUTOMATIC DISHWASHER, OR SPECIAL CONSIDERATION WITH |
| | SANITIZATION EQUIPMENT WITH 140 DEGREE DISCHARGE INTO |
| | THE DRAINAGE SYSTEM. 802.1.2 & 803.1. |
| | |
| | 4C) THE BAR AREA SHOWS ONLY A 3 INCH FLOOR DRAIN THERE |
| | IS NO MENTION OF A HUB DRAIN OR FLOOR SINK AS IN THE |
| | KITCHEN AREA PLEASE PROVIDE COMPLIANCE WITH 802.1.1 |
| | THRU 802.1.8. THE PLANS SHOW NO ICE MAKERS, ICE BENS |
| | ,,, |
| | |
| | 4D) THE PLAN SHOWS WHAT APPEARS TO BE EITHER A WALK IN |
| | FREEZER OR REFRIGARATOR BUT THERE IS NO CONSIDERATION |
| | FOR A FLOOR DRAIN NOR FOR CONDENSATE. PLEASE SHOW |
| | COMPLIANCE WITH 802.1..2. |
| | |
| | 4E) THE PLANS NEED ADDITIONAL INFORMATION FOR RESTROOMS |
| | 106 & 107, ( WOMENS NOT LABELED) SHOW THE 4 INCH |
| | SANITARY, THE PLANS DO NOT INDICATE IF THE WATER |
| | CLOSETS ARE TO BE WALL HUNG WITH THE SANITARY LINE |
| | ABOVE THE SLAB. THE SAME ISSUE WITH THE WASTE AND |
| | VENTING FOR THE LAVS THE PLANS DO NOT SHOWWHERE THE THE |
| | SANITARY PLUMBING DROPS BENEATH THE SLAB. PLEASE |
| | PROVIDE ADDITIONAL INFORMATION, 107.2.1.3 2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION, 2010 EDITION. A ISOMETRIC |
| | DRAWING WOULD GREATLY HELP. |
| | |
| | 4F) NOT REQUIRED. |
| | |
| | 5) SHEET PF1.04) |
| | |
| | 5A) ACROSS FROM THE GANGED RESTROOMS THERE APPEARS TO |
| | BE A FAMILY/ UNISEX RESTROOM THAT WILL MEET THE |
| | REQUIREMENTS OF FBC-P 403.5.2. DIRECTLY TO THE LEFT OF |
| | THIS UNISEX RESTROOM THERE IS A SINGLE TOLIET ROOM WITH |
| | OUT A LAVATORY, FL ACCESSIBILITY CODE 604.8.1.6 |
| | LAVATORY. IN NEW CONSTRUCTION, THE WHEELCHAIR |
| | ACCESSIBLE TOILET COMPARTMENT SHALL CONTAIN AN |
| | ACCESSIBLE LAVATORY WITHIN IT, WHICH MUST BE AT LEAST |
| | 19 INCHES WIDE BY 17 INCHES DEEP, NOMINAL SIZE, AND |
| | WALL-MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT |
| | TO OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY |
| | SECTION 604 FOR THE WHEELCHAIR ACCESSIBLE TOILET |
| | COMPARTMENT AND SHALL COMPLY WITH SECTION 606. SUCH |
| | LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED |
| | FIXTURE COUNT FOR THE BUILDING. SEE ALSO SECTION |
| | 213.3.4. |
| | ADVISORY 604.8.1.6 LAVATORY AND 604.8.1.7 WATER CLOSET. |
| | |
| | FLORIDA LAW, SECTION 553.504(5), F.S., STIPULATES THAT |
| | ??REQUIRED BATHING ROOMS AND TOILET ROOMS IN NEW |
| | CONSTRUCTION SHALL BE DESIGNED AND CONSTRUCTED?? WITH |
| | AN ACCESSIBLE LAVATORY IN THE WHEELCHAIR ACCESSIBLE |
| | COMPARTMENT AND THE WATER CLOSET LOCATED IN A CORNER |
| | DIAGONAL TO THE DOOR. THE ADA STANDARDS FOR ACCESSIBLE |
| | DESIGN AND THEREFORE THIS CODE REQUIRE WHEELCHAIR |
| | ACCESSIBLE COMPARTMENTS IN NEW CONSTRUCTION AND IN |
| | ALTERATIONS OF EXISTING BUILDINGS TO HAVE SELF CLOSING |
| | DOORS. WHILE THE FLORIDA LAVATORY REQUIREMENT AND WATER |
| | CLOSET PLACEMENT APPLY ONLY TO NEW CONSTRUCTION, THEY |
| | ARE DESIRABLE FOR ALL WHEELCHAIR ACCESSIBLE |
| | COMPARTMENTS AND SHOULD BE CONSIDERED WHERE FEASIBLE. |
| | |
| | 5B) WITHIN THE WOMENS RESTROOM (116) THERE ARE MORE |
| | THAN 6 WATERCLOSETS THAT WILL REQUIRE ONE AMBULATORY |
| | WATERCLOSET, NOTE THAT THESE STALLS ARE BETWEEN 35-37 |
| | INCHES IN WIDTH IT WILL THROUGH OFF ALL THE LAYOUT OF |
| | THE WATERCLOSETS IF NOT SHOWN OR NOTED 2010 FL |
| | ACCESSIBILITY CODE 604.8.1. |
| | |
| | 5C) SAME COMMENT AS BEFORE PLEASE PROVIDE ADDITIONAL |
| | INFORMATION AS TO IF THE WATER CLOSTES ARE WALL HUNG |
| | AND THE SANITARY IS ABOVE THE FLOOR AND PROVIDE A |
| | ISOMETRIC OF THE SANITARY FOR THIS AREA ALSO INCLUDE |
| | VENTING FOR THE SANITARY SYSTEM. |
| | |
| | 5D) NOT REQUIRED. |
| | |
| | 5E) SAME COMMENT AS BEFORE FOR THE KITCHEN, PLEASE |
| | IDENTFY ALL PLUMBING FIXTURES & EQUIPMENT WITH THE |
| | KITCHEN AND BAR AREA TO KNOW WHAT THE REQUIREMENTS ARE |
| | FOR BOTH THE INDIRECT WASTE REQUIREMENTS FOUND IN 802 |
| | AND THE REQUIREMENTS FOR SIZING REQUIREMENTS FOUND FOR |
| | SIZING OF THE GREASE INTERCEPTOR IN SECTION 1003.3.4 & |
| | TABLE 1003.5.1, INCLUDE THE LOADING FACTOR, PLEASE |
| | PROVIDE METHOD FOR SIZING. |
| | |
| | 6) 1/26/2014 WITHIN THIS REVIEW THERE ARE NO GAS PLANS |
| | TO REVIEW. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |