| 2014-01-15 15:57:31 | 600 OKEECHOBEE BOULEVARD |
| | PERMIT #13121042 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | SHEET C4.01: PROIVDE FIRE LANE SIGNAGE AND PAINTED |
| | CURBING (RED OR YELLOW) ALONG SOUTH ROSEMARY AVENUE AND |
| | ALONG THE SOUTHSIDE OF THE HOTEL (ENTRANCE TO |
| | CONVENTION CENTER PARKING LOT & DROP-OFF LOOP). PER |
| | SECTION 18.2.3.5.3 (NFPA 1), FIRE LANES SHALL BE MARKED |
| | WITH FREESTANDING SIGNS READING, ?FIRE LANE - NO |
| | PARKING BY ORDER OF THE FIRE DEPARTMENT.? SIGNS SHALL |
| | BE 12? X 18? WITH A WHITE BACKGROUND AND RED LETTERS |
| | AND SHALL BE A MAXIMUM OF SEVEN FEET IN HEIGHT TO THE |
| | BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE |
| | TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60 FEET APART. |
| | |
| | SHEET C5.01: PER NFPA 14 SECTION 7.12.2, HIGH-RISE |
| | BUILDINGS SHALL HAVE AT LEAST TWO REMOTELY LOCATED FIRE |
| | DEPARTMENT CONNECTIONS FOR EACH ZONE. |
| | |
| | SHEET C5.02: FIRE LINE PIVS ARE LOCATED WITHIN 40 FEET |
| | OF THE BUILDING. PER NFPA 24 SECTION 6.2.11 ALL |
| | CONNECTIONS TO PRIVATE FIRE SERVICE MAINS FOR FIRE |
| | PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH |
| | ONE OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED: |
| | (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40 |
| | FEET FROM THE BUILDING. |
| | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST |
| | INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED |
| | CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE |
| | BUILDING AS THE HEIGHT OF THE WALL FACING THE POST |
| | INDICATOR VALVE. |
| | (2) A WALL POST INDICATOR VALVE |
| | (3) AN INDICATING VALVE IN A PIT, INSTALLED IN |
| | ACCORDANCE WITH SECTION 6.4 |
| | (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING |
| | VALVE NOT LESS THAN 40 FEET FROM THE BUILDING. |
| | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A |
| | BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE |
| | SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET |
| | BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF |
| | THE WALL FACING THE BACKFLOW PREVENTER. |
| | (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM |
| | ACCESSIBLE FROM THE EXTERIOR |
| | (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE |
| | ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE |
| | AUTHORITY HAVING JURISDICTION |
| | |
| | GENERAL: INDICATE THE ADDRESS OF THE NEW PARKING |
| | STRUCTURE. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | FIRE INVESTIGATOR & INSPECTOR |