2014-01-15 15:57:31600 OKEECHOBEE BOULEVARD
 PERMIT #13121042
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET C4.01: PROIVDE FIRE LANE SIGNAGE AND PAINTED
 CURBING (RED OR YELLOW) ALONG SOUTH ROSEMARY AVENUE AND
 ALONG THE SOUTHSIDE OF THE HOTEL (ENTRANCE TO
 CONVENTION CENTER PARKING LOT & DROP-OFF LOOP). PER
 SECTION 18.2.3.5.3 (NFPA 1), FIRE LANES SHALL BE MARKED
 WITH FREESTANDING SIGNS READING, ?FIRE LANE - NO
 PARKING BY ORDER OF THE FIRE DEPARTMENT.? SIGNS SHALL
 BE 12? X 18? WITH A WHITE BACKGROUND AND RED LETTERS
 AND SHALL BE A MAXIMUM OF SEVEN FEET IN HEIGHT TO THE
 BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE
 TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60 FEET APART.
  
 SHEET C5.01: PER NFPA 14 SECTION 7.12.2, HIGH-RISE
 BUILDINGS SHALL HAVE AT LEAST TWO REMOTELY LOCATED FIRE
 DEPARTMENT CONNECTIONS FOR EACH ZONE.
  
 SHEET C5.02: FIRE LINE PIVS ARE LOCATED WITHIN 40 FEET
 OF THE BUILDING. PER NFPA 24 SECTION 6.2.11 ALL
 CONNECTIONS TO PRIVATE FIRE SERVICE MAINS FOR FIRE
 PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH
 ONE OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED:
 (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
 (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 GENERAL: INDICATE THE ADDRESS OF THE NEW PARKING
 STRUCTURE.
  