Plan Review Notes
Plan Review Notes For Permit 13121042
Permit Number 13121042
Review Stop B
Sequence Number 1
Notes
Date Text
2014-01-11 11:42:39BUILDING PLAN REVIEW
 PERMIT:13121042
 ADD: 600 OKEECHOBEE BLVD.
 EARTHWORK & FOUNDATION PERMIT
 P. B. CONVENTION CENTER HILTON HOTEL
 CONT: COASTAL CONSTRUCTION
 E;MAIL : NO CONTACT INFORMATION GIVEN
 TEL: (561) 630-3770
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. JAN. 11/ 2014
 ACTION: DENIED
  
 COASTAL CONSTRUCTION: THE TELEPHONE NUMBER WE ON FILE
 FOR BUSINESS IS NON-WORKING NUMBER. WE ALSO DO NOT HAVE
 A E-MAIL ADDRESS TO BE ABLE TO SEND REQUIRED FORMS AND
 INFORMATION DURING THE LIFR OF THIS PROJECT.
  
 NOTE: THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 1A) COMPLETED. WRITTEN THRESHOLD INSPECTION PLAN.
 S-0.02 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A WRITTEN STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 1B) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 1C) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. CONTACT KEN CONRAD MANAGER OF
 THE SPECIAL INSPECTOR PROGRAM AT (561)805-6666 FOR
 FURTHER INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
 1C)(1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected], TEL: 561-805-6715
  
 1C)(2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 1D) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 2) * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 110.7 IMPACT OF CONSTRUCTION. ALL CONSTRUCTION ACTIVITY
 REGULATED BY THIS CODE SHALL BE PERFORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF ADJACENT
 PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT GRANTED BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS OR CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES, BUT IS NOT LIMITED TO, THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFFS, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL
 NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS,
 POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR ITEMS, ON
 EXISTING PROPERTIES RESULTING IN A SIGNIFICANT DECREASE
 OF PERMEABLE LAND AREA ON ANY PARCEL OR HAS ALTERED THE
 DRAINAGE FLOW ON THE DEVELOPED PROPERTY SHALL, AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 3) THIS CYCLE OF REVIEW, NO SOILS REPORTS WERE
 UPLOADED. SHEET S0.00 FOUNDATION NOTES 1 & 2 INDICATE A
 SOILS REPORT HAS BEEN COMPLETED AND CONTAINED IN THE
 GEOTECHNICAL ENGINEERING STUDY, CITY PLACE CONVENTION
 CENTER HOTEL-GARAGE BY LANGAN DATED 06/05/13. PLEASE
 PROVIDE REPORT FOR REVIEW, AND RECOMMONDATIONS.
 2010 FBC-B
 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 4) SHEET S1.00 THE POOL EQUIPMENT STRUCTURE HAS A NOTE
 THAR THE FINISH FLOOR SLAB WILL BE AT 10'-8" ABOVE
 NGVD, THE ARCHITECTURAL SHEET A-2.0 INDICATES THE GRADE
 IS APPROXIMATELY 25'-0" NGVD OR OVER 17'-0" DIFFERENCE
 IN ELEVATION AT THE BOTTOM OF THE FOUNDATION THE
 DISTANCE IS 13'-11" FROM THE WEST PROPERTY LINE, PLEASE
 PROVIDE COMPLIANCE WITH 2010 FBC-B 3307.1 PROTECTION OF
 ADJOINING PROPERTY.
  
 5) FOR ALL EXCAVATION AND FILL ON THE JOBSITE HOW AND
 WHERE WILL THE FILL OR SURCHARGE BE STORED AND IN
 COMPLIANCE WITH 3304.1.1 SLOPE LIMITS AND 3304.1.2
 SURCHARGE.
  
 6A) PLEASE PROVIDE COMPLIANCE IN CREATING A SECURE SITE
 AND IN COMPLIANCE WITH3306.1 PROTECTION OF PEDESTRINS.
 3306.5 BARRIERS
 6B) . COMPLY WITH 3306.5 AND 3306.6.
  
 7) PLEASE PROVIDE COMPLIANCE WITH 3305.1 FACILITIES
 REQUIRED. SANITARY FACILITIES SHALL BE PROVIDED DURING
 CONSTRUCTION, REMODELING OR DEMOLITION ACTIVITIES IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 8) 3309.2 FIRE HAZARDS. THE PROVISIONS OF THIS CODE AND
 THE FLORIDA FIRE PREVENTION CODE SHALL BE STRICTLY
 OBSERVED TO SAFEGUARD AGAINST ALL FIRE HAZARDS
 ATTENDANT UPON CONSTRUCTION OPERATIONS. LOCATION OF
 FIRE EXTINGUISHERS IN ACCORDANCE WITH 906.
  
 9) SHEET S4.03 PROVIDES TYPICAL 16 INCH AUGER CAST PILE
 DETAILS FOR BOTH COMPRESSION AND TENSION PILES THE
 CHARTS SHOW ACTUAL STEEL LENGTH BUT NOT THE ACTUAL
 LENGTH OF THE AUGERED PILE? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 10) COMMENT 01/26/2014. FROM PLUMBING REVIEW. BASEMENT
 ELEVATION DOES NOT INDICATE A REQUIRED SUMP PIT,
 MISSING SIZE OF PIT AND LOCATION REQUIRED TO LIFT
 SANITARY TO NEXT LEVEL SEE PF-1.00 FOR LOCATION.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 11) COMMENT 01/26/2014 FROM PLUMBING REVIEW. SERVICE
 ELEVATOR (B016) & ELEVATOR MACHINE ROOM (B001) THE
 PLANS DO NOT INDICATE THE TYPE OF ELEVATOR TO BE
 INSTALLED IF HYDROLIC ELEVATORS ARE TO BE INSTALLED
 COMPLIANCE WIH 2010 FBC-B 3004.4 PLUMBING AND
 MECHANICAL SYSTEMS. PLUMBING AND MECHANICAL SYSTEMS
 SHALL NOT BE LOCATED IN AN ELEVATOR SHAFT.
 EXCEPTION: FLOOR DRAINS, SUMPS AND SUMP PUMPS SHALL BE
 PERMITTED AT THE BASE OF THE SHAFT PROVIDED THEY ARE
 INDIRECTLY CONNECTED TO THE PLUMBING SYSTEM.
  
 12) COMMENT 01/26/2014 FROM PLUMBING PLAN REVIEW.
 2010 FBC-B 424.1.6.1.3 SANITARY FACILITY FLOORS.
 FLOORS OF SANITARY FACILITIES SHALL BE CONSTRUCTED OF
 CONCRETE OR OTHER NONABSORBENT MATERIALS, SHALL HAVE A
 SMOOTH, SLIP-RESISTANT FINISH, AND SHALL SLOPE TO FLOOR
 DRAINS. CARPETS, DUCKBOARDS AND FOOTBATHS ARE
 PROHIBITED. THE INTERSECTION BETWEEN THE FLOOR AND
 WALLS SHALL BE COVERED WHERE EITHER FLOOR OR WALL IS
 NOT MADE OF WATERPROOF MATERIALS SUCH AS TILE OR VINYL.
 2010 FBC-P 403.6.3 SANITARY FACILITY FLOORS.
 FLOORS OF SANITARY FACILITIES SHALL BE CONSTRUCTED OF
 CONCRETE OR OTHER NONABSORBENT MATERIALS, SHALL HAVE A
 SMOOTH, SLIP-RESISTANT FINISH, AND SHALL SLOPE TO FLOOR
 DRAINS. CARPETS, DUCKBOARDS AND FOOT-BATHS ARE
 PROHIBITED. THE INTERSECTION BETWEEN THE FLOOR AND
 WALLS SHALL BE COVED WHERE EITHER FLOOR OR WALL IS NOT
 MADE OF WATERPROOF MATERIALS SUCH AS TILE OR VINYL.
  
  
  
  
 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  