2013-12-27 10:59:40PERMIT #13121015
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ****PROVISO****
 ADDITONAL DEVICE NEEDED IN THE STOCKROOM TO MEET
 COVERAGE REQUIREMENTS OR CURRENT DEVICES SHOULD BE
 RAISED TO 110CD (CURRENTLY SET AT 75CD).
 THIS IS TO BE VERIFIED DURING FIELD INSPECTION. SEE
 NOTE ON PLAN FOR EXACT LOCATION.
 *******************
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
  