| 2014-01-07 14:52:24 | 344 COURTNEY LAKES CIRCLE |
| | PERMIT #13120986 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | *****PROVISO - SUBMIT REVISION***** |
| | |
| | SUBMIT STAIR, HANDRAIL AND GUARDRAIL DETAILS FOR ACCESS |
| | TO THE CONSTRUCTION TRAILER. HANDRAILS ARE REQUIRED ON |
| | BOTH SIDES OF THE STAIR. HANDRAILS SHALL BE LOCATED NOT |
| | LESS THAN 34 INCHES AND NOT MORE THAN 38 INCHES ABOVE |
| | THE SURFACE OF THE TREAD, MEASURED VERTICALLY TO THE |
| | TOP OF THE RAIL FROM THE LEADING EDGE OF THE TREAD. |
| | HANDRAIL ENDS SHALL BE RETURNED TO THE WALL OR FLOOR OR |
| | SHALL TERMINATE AT NEWEL POSTS. HANDRAIL CROSS SECTION |
| | SHALL HAVE A DIAMETER OF NOT LESS THAN 1.25 INCHES AND |
| | NOT MORE THAN 2 INCHES. |
| | GUARDS, AT LEAST 42-INCHES TALL, SHALL BE PROVIDED AT |
| | THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, MEZZANINE, |
| | ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. OPEN |
| | GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH DIAMETER |
| | SPHERE UP TO A HEIGHT OF 34-INCHES. THE TRIANGULAR |
| | OPENINGS FORMED BY THE RISER, TREAD AND BOTTOM ELEMENT |
| | OF THE GUARDRAIL SHALL PROHIBIT THE PASSAGE OF A 6-INCH |
| | DIAMETER SPHERE. STAIR RISERS SHALL BE BETWEEN 4 INCHES |
| | AND 7 INCHES IN HEIGHT. STAIRS SHALL BE SLIP RESISTANT |
| | AND HAVE A MINIMUM TREAD DEPTH OF 11 INCHES AND PREVENT |
| | THE ACCUMULATION OF WATER. |
| | |
| | PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, |
| | ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2 |
| | TEMPORARY CONSTRUCTION TRAILERS SHALL BE SEPARATED FROM |
| | ADJACENT TRAILERS OR STRUCTURES IN ACCORDANCE WITH |
| | TABLE 4.2.1. PER TABLE 4.2.1: |
| | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |