Plan Review Notes
Plan Review Notes For Permit 13120969
Permit Number 13120969
Review Stop B
Sequence Number 3
Notes
Date Text
2014-02-24 16:15:50****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 2010
  
 1. THE DOORS PROPOSED DO NOT INCLUDE PANIC DEVICES (SEE
 PREVIOUS LIST FOR CODE REFERENCES). THE PANIC DEVICE
 PROPOSED IS NOT LISTED (SEE FBC 1008.1.10.1) AND
 RETROFIT OF THE PROPOSED PANIC DEVICE ON TO THE
 PROPOSED DOORS WOULD VIOLATE THE PRODUCT APPROVAL (WIND
 RESISTANCE REQUIREMENTS AND TESTING, FBC 1609).
  
 THIS HAS BEEN CONFIRMED WITH THE MANUFACTURER OF THE
 DOOR. PLEASE SELECT A DOOR WHICH HAS BEEN TESTED WITH A
 UL LISTED PANIC DEVICE.
  
  