Plan Review Notes
Plan Review Notes For Permit 13120940
Permit Number 13120940
Review Stop B
Sequence Number 1
Notes
Date Text
2013-12-20 17:04:28RESIDENTIAL (R3) ROOFING REVISION BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 ***NOTES:
 A)THIS PROPERTY IS LOCATED IN THE HISTORIC DISTRICT.
 REVISION NEEDS TO BE APPROVED BY HISTORIC. SEE HISTORIC
 COMMENTS.
 B) OWES $10 FOR HISTORIC REVIEW FEE.
  
 1- SELECTED ASSEMBLY W-16 FROM FLORIDA PRODUCT APPROVAL
 FL10497-R2 SUBMITTED DOESN'T MEET THE DESIGN PRESSURES
 REQUIRED BY SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL.
 THE DESIGN PRESSURES ON THE CORNERS OF THE ROOF ARE
 HIGHER THAN THE DESIGN PRESSURES LISTED ON THE SELECTED
 ASSEMBLY.
 NEED TO USE ANOTHER ASSEMBLY THAT MEETS THE DESIGN
 PRESSURES.
 ***NOTE: BONDED ROOF ASEMBLY DOENS'T ALLOW NAIL
 ENHANCING. SEE LIMITATION 5.7 ON PAGE 3 OF 4 OF PRODUCT
 APRPOVAL SUBMITTED.
  