| 2014-01-15 12:03:50 | FUEL GAS PLAN REVIEW |
| | PERMIT: 13120929 |
| | ADDRESS: 1815 PALM BEACH LAKES BLDG "FOUNDATION" |
| | CONT: EMJ |
| | TEL: (423) 855-6857 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JAN. 15/ 2014 |
| | ACTION: DENIED |
| | |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | |
| | 1) A SEPARATE GAS PERMIT IS REQUIRED, IT IS NOT COVERED |
| | UNDER THE PLUMBING PERMIT OR PLAN REVIEW, THIS IS FOR |
| | THE FOUNDATION ONLY. |
| | |
| | 2) SHEET P101 NOTE # 9 INDICTES UNDERGROUND GAS LINE, |
| | METER AND REGULATOR SHALL BE PROVIDED AND INSTALLED BY |
| | THE GAS UTILITY COMPANY. NOTE # 10 GAS CAPPED FOR |
| | FUTURE TENANT CONNECTION. VERIFY TENANT GAS LOAD DEMAND |
| | & PRESSURE REQUIREMENTS WITH TENANT IMPROVEMENT PLAN |
| | PROR TO THE INSTALATION OF GAS LINE. |
| | |
| | 2A) IT IS NOT CLEAR AS TO WHERE FLORIDA GAS UTIULITIES |
| | METER IS TO BE SET. IT APPEARS THAT THE GAS LINES ARE |
| | TO BE TONEATH THE SLAB. PLEASE REVIEW 2010 FBC-GAS |
| | SECTIONS : |
| | 404.4 UNGROUND PENETRATIONS PROHIBITED, AND 404.6 |
| | PIPING IN SOLID FLOORS. |
| | |
| | 2B) NOTE # 10 INDICATES THE GAS PIPE IS TO BE SIZED FOR |
| | FUTURE TENANT CONNECTION. VERIFY TENANT GAS LOAD DEMAND |
| | & PRESSURE REQUIREMENTS WITH TENANT IMPROVEMENT PLAN |
| | PROR TO THE INSTALATION OF GAS LINE. GAS IS TO BE SIZED |
| | TO THE MAXIMUM DEMAND 402.2.PROVIDE SIZING METHOD AND |
| | TABLES FOR SIZING OF PIPE AND DEVELOPED LENGTH. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |