Plan Review Notes
Plan Review Notes For Permit 13120929
Permit Number 13120929
Review Stop G
Sequence Number 1
Notes
Date Text
2014-01-15 12:03:50FUEL GAS PLAN REVIEW
 PERMIT: 13120929
 ADDRESS: 1815 PALM BEACH LAKES BLDG "FOUNDATION"
 CONT: EMJ
 TEL: (423) 855-6857
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: WED. JAN. 15/ 2014
 ACTION: DENIED
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
  
 1) A SEPARATE GAS PERMIT IS REQUIRED, IT IS NOT COVERED
 UNDER THE PLUMBING PERMIT OR PLAN REVIEW, THIS IS FOR
 THE FOUNDATION ONLY.
  
 2) SHEET P101 NOTE # 9 INDICTES UNDERGROUND GAS LINE,
 METER AND REGULATOR SHALL BE PROVIDED AND INSTALLED BY
 THE GAS UTILITY COMPANY. NOTE # 10 GAS CAPPED FOR
 FUTURE TENANT CONNECTION. VERIFY TENANT GAS LOAD DEMAND
 & PRESSURE REQUIREMENTS WITH TENANT IMPROVEMENT PLAN
 PROR TO THE INSTALATION OF GAS LINE.
  
 2A) IT IS NOT CLEAR AS TO WHERE FLORIDA GAS UTIULITIES
 METER IS TO BE SET. IT APPEARS THAT THE GAS LINES ARE
 TO BE TONEATH THE SLAB. PLEASE REVIEW 2010 FBC-GAS
 SECTIONS :
 404.4 UNGROUND PENETRATIONS PROHIBITED, AND 404.6
 PIPING IN SOLID FLOORS.
  
 2B) NOTE # 10 INDICATES THE GAS PIPE IS TO BE SIZED FOR
 FUTURE TENANT CONNECTION. VERIFY TENANT GAS LOAD DEMAND
 & PRESSURE REQUIREMENTS WITH TENANT IMPROVEMENT PLAN
 PROR TO THE INSTALATION OF GAS LINE. GAS IS TO BE SIZED
 TO THE MAXIMUM DEMAND 402.2.PROVIDE SIZING METHOD AND
 TABLES FOR SIZING OF PIPE AND DEVELOPED LENGTH.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  