| Date |
Text |
| 2014-01-25 08:41:56 | BUILDING PLAN REVIEW |
| | PERMIT: 13120923 |
| | ADD: 1703 PALM BEACH LAKES / SHELL BUILDING |
| | CONT: EMJ |
| | TEL: (561) 373-3902 |
| | CONTACT: KARI |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: SATURDAY JAN. 25/ 2014 |
| | ACTION:BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | |
| | 1) THE COVER SHEET BUILDING & CONSTRUCTION DATA UNDER |
| | THE HEADING FIRE PROTECTION SYSTEM SPRINKLERS FBC903 |
| | DESIGN STANDARD NFPA 13. NOTE NEITHER THE DRAWING INDEX |
| | NOR THE 40 SHEETS SUBMITTED ELECTRONICALLY SHOW ANY |
| | FIRE SPRINKLER PLANS. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 107.3.5.1.1(5) FIRE SPRINKLER SCHEMATIC. |
| | |
| | 2) MISSING COMPLIANCE FORMS FOR 2010 FL ENERGY CODE FOR |
| | SHELL BUILDINGS: |
| | 103.2 INFORMATION ON CONSTRUCTION DOCUMENTS. 103.2.1 |
| | CODE DEMONSTRATION FORMS. SEE TABLE 103.2.1. |
| | |
| | 3) ROOF NOTES, NO ACTION REQUIRED!!! |
| | |
| | SHEET A141 ROOF PLAN INDICATES ZONE # 1 TO BE |
| | MECHANICALLY FASTENED, NOTE ON PLAN ZONES 2 & 3 THE |
| | ROOFING IS TO BE FULLY ADHERED SINGLE PLY TPO. |
| | |
| | NOA 12-0514.04 FIRESTONE 1-30 PAGES TPO OVER STEEL DECK |
| | PAGE 12 HIGHLIGHTED SINGLE PLY TPO, STEEL INSULATED |
| | DECK 22 GAUGE/ 6'-0" SPACING |
| | ISO 95+GL MIN 2" THICK MAXIMUM DESIGN FOR MECH FASTENED |
| | -75 PSI |
| | ROOF ZONE PRESSURES VASD 10 SQ FT -65.1 |
| | NOTE NO ROOF ZONE 3, THE PARAPETS ARE OVER 3'-0" HIGH. |
| | |
| | |
| | |
| | |
| | |
| | |