2013-12-26 15:20:58460 SOUTH ROSEMARY AVENUE - SUITE #186
 PERMIT #13120890
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 MAIN ENTRANCE DOOR: AS A SUBSTITUTE FOR PANIC HARDWARE,
 THE MAIN ENTRANCE IS PERMITTED TO HAVE AN INTERIOR
 KEYED DOOR LOCK (AND NO LATCH) WITH A READILY VISIBLE
 SIGN STATING THIS DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1
 INCH IN HEIGHT. KEYED LOCK TO BE EQUIPPED WITH AN
 "OPEN/LOCKED" INDICATOR WINDOW (SUCH AS ADAMS RITE 4089
 OR SIMILAR). A THUMB TURN STYLE LOCK IS NOT PERMITTED
 TO BE SUBSTITUTED FOR A KEYED LOCK.
  
 SECONDARY EXIT DOORS: FOR ASSEMBLY OCCUPANCIES WITH AN
 OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER
 THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE
 PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER
 LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE
 RELEASED BY THE PANIC HARDWARE. A KEYED LOCK IS NOT
 PERMITTED AS THIS IS NOT THE MAIN ENTRANCE/EXIT.
  
 IF NOT ALREADY EXISTING, PROVIDE AN EXTERIOR KEY SAFE
 TO ALLOW EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO
 THE BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN
 BE ORDERED FROM WWW.KNOXBOX.COM.
  
 SEPARATE PLANS AND PERMITS NEEDED TO MODIFY EXISTING
 FIRE ALARM SYSTEM, SPRINKLER SYSTEM AND KITCHEN HOOD
 SUPPRESSION SYSTEM.
  