| 2014-01-15 17:33:31 | 3501 ELECTRONICS WAY - PHASE 4A | | | PERMIT #13120879 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SHEET E5.0: EMERGENCY LIGHTING PHOTOMETRICS INDICATES | | | LESS THAN 1 FOOT-CANDLE (NORMAL) AND LESS THAN 10 | | | FOOT-CANDLES (EMERGENCY) ON THE EGRESS STAIRS. PER NFPA | | | 101 SECTION 7.8.1.3. DURING CONDITIONS OF USE, THE | | | MINIMUM ILLUMINATION FOR NEW STAIRS SHALL BE AT LEAST | | | 10 FOOT-CANDLES MEASURED AT THE WALKING SURFACE. DURING | | | CONDITIONS OF NON-USE THE STAIRS SHALL BE PROVIDED WITH | | | AT LEAST 1 FOOT-CANDLE. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|