| Notes |
| Date |
Text |
| 2014-01-07 20:16:06 | THIS APPLICATION WAS CONDITIONALLY APPROVED AS FOLLOWS: | | | PROVISO: | | | AS PER FBC-B SECTION 907 | | | A SMOKE DETECTOR IS REQUIRED | | | IN THE ELECTRICAL ROOM. | | | AS THIS ADDITION ALTERS THE RISER | | | DIAGRAM, A REVISED RISER | | | DIAGRAM SHOWING THE ADDED | | | DEVICE ALONG WITH THE REVISED | | | LOAD AND BATTERY CALCS SHALL | | | BE SUBMITTED FOR APPROVAL | | | PRIOR TO FINAL INSPECTION. | | | |
|