| Plan Review Notes For Permit 13120835 |
| Permit Number |
13120835 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-06-30 10:03:25 | 2010 FBC | | | | | | GAS PLAN IS DENIED | | | | | | 1) BASED ON THE GAS RISER PLAN THAT WAS SUBMITTED, THE | | | LONGEST PIPE RUN FROM THE POINT OF DELIVERY TO THE MOST | | | REMOTE OUTLET IS 165 FEET AND THE TOTAL LOAD ON THE | | | SYSTEM IS 1,221,000 BTU. THE 3/4" PE PIPE THAT IS | | | SPECIFIED IS TOO SMALL. IT IS RATED FOR 791,000 BTU 175 | | | FEET PER FBCR TABLE G2413.4(8) & TABLE 402.4(20). 1" PE | | | PIPE WILL BE REQUIRED FROM THE POINT OF DELIVERY TO THE | | | POINT WHERE TO LOAD IS REDUCED TO 791,000 BTU FROM THAT | | | POINT IT CAN BE REDUCED TO 3/4" PE PIPE. PLEASE | | | CORRECT. | | | | | | 2) THE LENGTH OF THE BRANCH PIPE SECTION, SIZE AND PIPE | | | MATERIAL IS NOT SPECIFIED ON THE PLAN FOR THE BBQ. FBCR | | | G2413 (402) | | | | | | 3) THE LENGTH OF THE BRANCH PIPE SECTION, AND PIPE | | | MATERIAL IS NOT SPECIFIED ON THE PLAN FOR THE POOL | | | HEATER. FBCR G2413 (402) | | | | | | 4) THE LENGTH OF THE BRANCH PIPE SECTION AND PIPE | | | MATERIAL IS NOT SPECIFIED ON THE PLAN FOR THE FUTURE | | | DRYER. FBCR G2413 (402) | | | | | | 5) THE NAME, SIGNATURE AND LICENSE NUMBER OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN IS REQUIRED ON THE GAS RISER | | | PLANS. CITY AMENDMENTS 107.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|