2014-01-14 08:21:252010 FBC
  
 DENIED
  
 1) SUBMIT TWO LEGIBLE SETS OF A GAS RISER DIAGRAM. THE
 ONES THAT WERE SUBMITTED ARE NOT CLEAR ENOUGH TO BE
 FILED FOR PUBLIC RECORD. CITY AMENDMENTS 107.2.1.4
  
 2) SPECIFY THE DISTANCE FROM EACH SECOND STAGE
 REGULATOR TO THE APPLIANCE, THE PIPING MATERIAL AND
 SIZE PER .5 PSI TABLES. FBCFG 401.8
  
 3) SUBMIT THE SPEC. SHEET FOR THE GAS FIRE PLACE
 EQUIPMENT SHOWING THAT ONLY THE 25,000 BTUS THAT ARE
 SPECIFIED ON THE GAS PLAN IS REQUIRED. OTHERWISE THE
 80,000 BTUS SPECIFIED IN FBC FUEL GAS TABLE 402.2 FOR
 GAS LOGS SHALL BE USED. FBCFG 402.2
  
 4) SUBMIT THE MANUFACTURER'S SPECIFICATIONS THAT
 INDICATE THE REQUIRED BTUS FOR THE GENERATOR. THE
 INFORMATION I GOT ON LINE IS 240,000 BTUS FOR NATURAL
 GAS. 225.000 BTUS IS WHAT IS SPECIFIED ON THE GAS
 DRAWING.
  