| Plan Review Notes For Permit 13120835 |
| Permit Number |
13120835 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-01-14 08:21:25 | 2010 FBC | | | | | | DENIED | | | | | | 1) SUBMIT TWO LEGIBLE SETS OF A GAS RISER DIAGRAM. THE | | | ONES THAT WERE SUBMITTED ARE NOT CLEAR ENOUGH TO BE | | | FILED FOR PUBLIC RECORD. CITY AMENDMENTS 107.2.1.4 | | | | | | 2) SPECIFY THE DISTANCE FROM EACH SECOND STAGE | | | REGULATOR TO THE APPLIANCE, THE PIPING MATERIAL AND | | | SIZE PER .5 PSI TABLES. FBCFG 401.8 | | | | | | 3) SUBMIT THE SPEC. SHEET FOR THE GAS FIRE PLACE | | | EQUIPMENT SHOWING THAT ONLY THE 25,000 BTUS THAT ARE | | | SPECIFIED ON THE GAS PLAN IS REQUIRED. OTHERWISE THE | | | 80,000 BTUS SPECIFIED IN FBC FUEL GAS TABLE 402.2 FOR | | | GAS LOGS SHALL BE USED. FBCFG 402.2 | | | | | | 4) SUBMIT THE MANUFACTURER'S SPECIFICATIONS THAT | | | INDICATE THE REQUIRED BTUS FOR THE GENERATOR. THE | | | INFORMATION I GOT ON LINE IS 240,000 BTUS FOR NATURAL | | | GAS. 225.000 BTUS IS WHAT IS SPECIFIED ON THE GAS | | | DRAWING. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|