| 2014-01-06 08:07:42 | BUILDING PLAN REVIEW |
| | PERMIT: 13120825 |
| | ADD: 5731 PREMIER PARK RD. |
| | CONT: ZIRKELBACH CONSTRUCTION |
| | TEL: (864)300-1013 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JAN. 06/2013 |
| | ACTION: DENIED |
| | |
| | 1A) THIS PROJECT BEING TILT-WALL CONSTRUCTION WILL |
| | REQUIRE A RESIDENT INSPECTOR. 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 2010 EDITION* 110.3.9 RESIDENT |
| | INSPECTOR. |
| | SUBMIT INSPECTOR RESUME' AND LICENSE DOCUMENTS TO KEN |
| | CONRAD, MANAGER OF THE RESIDENT INSPECTOR PROGRAM. A |
| | RESIDENT INSPECTOR PROGRAM IS REQUIRED, ON THIS |
| | PROJECT, DUE TO ONE OR MORE OF THE FOLLOWING: |
| | - BUILDINGS/ADDITIONS OF TYPE I OR II CONSTRUCTION |
| | - ANY MAJOR STRUCTURAL ALTERATIONS |
| | - STRUCTURES IN WHICH THE CONCRETE DESIGN IS BASED ON |
| | COMPRESSIVE STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| | - BUILDINGS OVER 20,000 SQ FT IN AREA |
| | - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS OF |
| | CONSTRUCTION (TILT WALL DESIGN). |
| | |
| | KEN CONRAD CONTACT INFORMATION: |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | RESIDENT INSPECTOR BOOKLET & FORMS WERE E-MAILED TO |
| | ANTHONY CAMPANO AT [email protected] |
| | 1/06/2014 07:46 AM. |
| | SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES |
| | WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE |
| | BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED |
| | ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER |
| | CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH |
| | INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS |
| | INCLUDING THE DAILY INSPECTIONS TO THE BUILDING |
| | OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF |
| | THE RESIDENT INSPECTOR. |
| | |
| | AT THE COMPLETION OF THE CONSTRUCTION WORK OR PROJECT, |
| | SUCH INSPECTORS SHALL SUBMIT A CERTIFICATE OF |
| | COMPLIANCE TO THE BUILDING OFFICIAL, STATING THAT THE |
| | WORK WAS DONE IN COMPLIANCE WITH THIS CODE AND IN |
| | ACCORDANCE WITH THE PERMITTED DRAWING. FINAL INSPECTION |
| | SHALL BE MADE BY THE BUILDING OFFICIAL BEFORE A |
| | CERTIFICATE OF OCCUPANCY OR CERTIFICATE OF COMPLETION |
| | IS ISSUED; AND CONFIRMATION INSPECTIONS MAY BE MADE AT |
| | ANY TIME TO MONITOR ACTIVITIES AND RESIDENT INSPECTORS. |
| | |
| | 1B) SINCE THIS PROJECT WILL REQUIRE A RESIDENT |
| | INSPECTOR (3) SETS OF PLANS, AND PRODUCT APPROVALS WILL |
| | BE REQUIRED. |
| | |
| | 2) * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 110.7 IMPACT OF CONSTRUCTION. ALL CONSTRUCTION ACTIVITY |
| | REGULATED BY THIS CODE SHALL BE PERFORMED IN A MANNER |
| | SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF ADJACENT |
| | PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT |
| | SAID PROPERTY PURSUANT TO A CONSENT GRANTED BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS OR CONDITIONS |
| | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| | INCLUDES, BUT IS NOT LIMITED TO, THE CONTROL OF DUST, |
| | NOISE, WATER OR DRAINAGE RUN-OFFS, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL HISTORIC |
| | SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, AND |
| | MAY REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE POSITIVE DRAINAGE |
| | PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| | DEVELOPERS, CONTRACTORS AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A SIGNIFICANT DECREASE OF |
| | PERMEABLE LAND AREA ON ANY PARCEL OR HAS ALTERED THE |
| | DRAINAGE FLOW ON THE DEVELOPED PROPERTY SHALL, AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE |
| | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| | OF THE FINAL INSPECTION. |
| | |
| | 3) THE STRUCTURAL SHEETS ENGINEERS SIGNATURE AND SEAL |
| | ARE ALL PHOTO-COPIES. PLANS, SPECIFICATIONS, REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND |
| | BEING FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE |
| | AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE |
| | DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | EFFECTIVE DATE 05/06/2009 |
| | (2)(A) EVERY SHEET OF PLANS AND PRINTS WHICH MUST BE |
| | SEALED UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL |
| | BE SEALED, SIGNED AND DATED BY THE PROFESSIONAL |
| | ENGINEER IN RESPONSIBLE CHARGE. |
| | |
| | 4) SHEET S-101 THE WIND DESIGN CRITERIA NEEDS |
| | CORRECTIONS, THERE IS A DISCREPANCY BETWEEN THE |
| | BUILDING IMPORTANCE FACTOR (BUILDING CATEGORY 2) AND |
| | THE WIND VELCITY (160 ULTIMATE). WE AGREE THIS IS A |
| | BUILDING CATEGORY 2 BUT WITH A ULTIMATE VELOCITY OF 170 |
| | MPH WIND VELOCITY , EXPOSURE C. |
| | |
| | 5) MISSING IN THE STRUCTURAL DESIGN ROOF FRAMING AND |
| | ROOF DECK DESIGN, PART OF THE BUILDING ENVELOPE. * 2010 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 107.3.5.1.1(8) MINIMUM REQUIREMENTS FOR COMMERCIAL PLAN |
| | REVIEW, BUILDING ENVELOPE/ ROOF FRAMING/ ROOF SYSTEMS. |
| | |
| | 6) MISSING IN THE STRUCTURAL DESIGN 2010 FBC-B 1609.1.1 |
| | DETERMINATION OF WIND DESIGN- CHAPTER 6 OF ASCE 7-10. |
| | |
| | 6A) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 6B) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | 6C) PLEASE PROVIDE PRESSURES IN BOTH VASD & VULT. NOTE |
| | PRODUCT APPROVALS INDICATE PRESSURES IN VASD. 2010 |
| | FBC-B 1609.1.5. |
| | |
| | 7) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) PRE-ENGINEERED A/C STANDS |
| | |
| | 8) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 9) SHEET A1.3 INDICATES THE EGRESS PLAN IS DESIGNED TO |
| | THE 2004 FBC-B, 2010 FBC- EXISTING BUILDING. 1001.1 |
| | SCOPE. AN ADDITION TO A BUILDING OR STRUCTURE SHALL |
| | COMPLY WITH THE FLORIDA BUILDING CODES AS ADOPTED FOR |
| | NEW CONSTRUCTION WITHOUT REQUIRING THE EXISTING |
| | BUILDING OR STRUCTURE TO COMPLY WITH ANY REQUIREMENTS |
| | OF THOSE CODES OR OF THESE PROVISIONS, EXCEPT AS |
| | REQUIRED BY THIS CHAPTER. WHERE AN ADDITION IMPACTS THE |
| | EXISTING BUILDING OR STRUCTURE, THAT PORTION SHALL |
| | COMPLY WITH THIS CODE. |
| | |
| | 10) SHEET A3.1, CUT SECTION THRU NEW OFFICE WALLS, |
| | DETAIL # 2/ A8.2 : |
| | 10A) 2010 FL EXISITNG BLDG CODE 1001.2 CREATION OR |
| | EXTENSION OF NONCONFORMITY. AN ADDITION SHALL NOT |
| | CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING |
| | BUILDING TO WHICH THE ADDITION IS BEING MADE WITH |
| | REGARD TO ACCESSIBILITY, STRUCTURAL STRENGTH, FIRE |
| | SAFETY, MEANS OF EGRESS, OR THE CAPACITY OF MECHANICAL, |
| | PLUMBING, OR ELECTRICAL SYSTEMS. |
| | THE COVER SHEET NOR A3.1 INDICATE HOW COMPLIANCE WITH |
| | OCCUPANCY SEPERATION IS OBTAINED AND COMPLIANCE WITH |
| | FBC-B TABLE 508.4. |
| | |
| | 10B) THIS DETAIL INDICATES INSULATION IN THE WALL THAT |
| | SEPERATES THE STORAGE OCCUPANCY FROM THE OFFICE AREA. |
| | 2010 EXIST BLDG CODE LEVEL II ALTERATIONS: 711.1 |
| | MINIMUM REQUIREMENTS. ALTERATIONS SUBJECT TO THIS |
| | CHAPTER SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, ENERGY CONSERVATION.101.4.1 |
| | EXISTING BUILDINGS. |
| | EXISTING BUILDINGS SHALL MEET THE CRITERIA IN TABLE |
| | 101.4.1 AS APPROPRIATE TO THE CONDITION DESCRIBED. IN |
| | TABLE 101.4.1 RENOVATION ENVELOPE TO MEET SECTION 502 . |
| | 502.1.1.1 SHELL BUILDINGS, RENOVATIONS AND ALTERATIONS. |
| | THE BUILDING THERMAL ENVELOPE SHALL MEET THE |
| | REQUIREMENTS OF TABLE 502.1.1.1(1) OR TABLE |
| | 502.1.1.1(2) |
| | |
| | 10C) PROVIDE COMPLIANCE WITH 2010 ENERGY CODE 502.2.1.2 |
| | CEILING INSULATION. INSULATION INSTALLED ON A SUSPENDED |
| | CEILING WITH REMOVABLE CEILING TILES SHALL NOT BE |
| | CONSIDERED PART OF THE MINIMUM THERMAL RESISTANCE OF |
| | THE ROOF INSULATION UNLESS THE ROOF/CEILING CAVITY IS |
| | SEALED FROM THE EXTERIOR ENVIRONMENT. |
| | 502.3.5.2 UNVENTED DROPPED CEILING CAVITIES. |
| | WHERE UNVENTED DROPPED CEILING CAVITIES OCCUR OVER |
| | CONDITIONED SPACES THAT DO NOT HAVE AN AIR BARRIER |
| | BETWEEN THE CONDITIONED AND UNCONDITIONED SPACE (SUCH |
| | AS T-BAR CEILINGS), THEY SHALL BE COMPLETELY SEALED |
| | FROM THE EXTERIOR ENVIRONMENT (AT THE ROOF PLANE) AND |
| | ADJACENT SPACES BY A CONTINUOUS AIR BARRIER THAT IS |
| | ALSO SEALED TO THE AIR BARRIER OF THE WALLS. IN THAT |
| | CASE, THE ROOF ASSEMBLY SHALL CONSTITUTE BOTH THE UPPER |
| | THERMAL ENVELOPE AND PRESSURE ENVELOPE OF THE BUILDING. |
| | |
| | 11) SHEET A1.3 & A2.1 SHOW 2 NEW LOADING DOORS 27 & 28, |
| | SHEET A9.2 DETAIL # 3 INDICATES CONCRETE WALL PANELS |
| | WHERE DETAIL 1,6 & 10 APPEAR THEY ARE FOR METAL |
| | BUILDING? |
| | DISCREPANCY IN THE PLANS. 107.2.1.3. ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |