| Plan Review Notes For Permit 13120817 |
| Permit Number |
13120817 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-02-08 09:48:57 | BUILDING PLAN REVIEW | | | PERMIT: 13120817 | | | ADD: 1801 PALM BEACH LAKES BLVD / GENERATOR | | | CONT: EMJ CORP | | | TEL: (561)423-414-1589 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2ND REVIEW | | | DATE: SAT. FEB. 08/2014 | | | ACTION: BUILDING PROVISO | | | | | | 1) SEPERATE PERMIT REQUIRED FOR GEN-ELECTRIC & GAS. | | | | | | NOTES KOHLER | | | MODEL: 60REZGB | | | NATURAL GAS | | | FUEL SUPPLY INLET 1 1/4 NPFT | | | NATURAL GAS/ LPG FUEL SUPPLY PRESSURE, KPA(IN. H2O) | | | 1.74-2.74 (7-11) | | | FUEL CONSUMPTION | | | FUEL CONSUMPTION @ 100% LOAD 22.4M3/HR. | | | | | | | | | GAS PLAN UNDER REV# 13120864 | | | SHEET P-403 | | | NATURAL GAS | | | INLET PRESSURE 2PSI SYSTEM | | | PRESSUE DROP 0.5 WC | | | S.G. 0.60 | | | SCHEDULE 40 METALLIC | | | LONGEST RUN 10' | | | MAX. LOAD 790,000 BTU | | | |
|