2014-02-08 09:50:21FUEL -GAS PLAN REVIEW
 PERMIT: 13120817
 ADD: 1801 PALM BEACH LAKES BLVD / GENERATOR
 CONT: EMJ CORP
 TEL: (561)423-414-1589
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: SAT. FEB. 08/2014
 ACTION: PASSED
  
 1) PROVISO: SEPERATE PERMIT REQUIRED FOR GEN-ELECTRIC &
 GAS.
  
 NOTES KOHLER
 MODEL: 60REZGB
 NATURAL GAS
 FUEL SUPPLY INLET 1 1/4 NPFT
 NATURAL GAS/ LPG FUEL SUPPLY PRESSURE, KPA(IN. H2O)
 1.74-2.74 (7-11)
 FUEL CONSUMPTION
 FUEL CONSUMPTION @ 100% LOAD 22.4M3/HR.
  
  
 GAS PLAN UNDER REV# 13120864
 SHEET P-403
 NATURAL GAS
 INLET PRESSURE 2PSI SYSTEM
 PRESSUE DROP 0.5 WC
 S.G. 0.60
 SCHEDULE 40 METALLIC
 LONGEST RUN 10'
 MAX. LOAD 790,000 BTU
  