Plan Review Notes For Permit 13120817 |
Permit Number |
13120817 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-02-08 09:50:21 | FUEL -GAS PLAN REVIEW | | PERMIT: 13120817 | | ADD: 1801 PALM BEACH LAKES BLVD / GENERATOR | | CONT: EMJ CORP | | TEL: (561)423-414-1589 | | | | 2010 FLORIDA BUILDING CODE W | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | 2ND REVIEW | | DATE: SAT. FEB. 08/2014 | | ACTION: PASSED | | | | 1) PROVISO: SEPERATE PERMIT REQUIRED FOR GEN-ELECTRIC & | | GAS. | | | | NOTES KOHLER | | MODEL: 60REZGB | | NATURAL GAS | | FUEL SUPPLY INLET 1 1/4 NPFT | | NATURAL GAS/ LPG FUEL SUPPLY PRESSURE, KPA(IN. H2O) | | 1.74-2.74 (7-11) | | FUEL CONSUMPTION | | FUEL CONSUMPTION @ 100% LOAD 22.4M3/HR. | | | | | | GAS PLAN UNDER REV# 13120864 | | SHEET P-403 | | NATURAL GAS | | INLET PRESSURE 2PSI SYSTEM | | PRESSUE DROP 0.5 WC | | S.G. 0.60 | | SCHEDULE 40 METALLIC | | LONGEST RUN 10' | | MAX. LOAD 790,000 BTU | | |
|