| Plan Review Notes For Permit 13120817 |
| Permit Number |
13120817 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-01-28 18:19:11 | THIS IS BEING CONDITIONALLY APPROVED AS FOLLOWS: | | | AS PER NEC 445.13 THE AMPACITY OF THE CONDUCTOR FROM | | | THE GENERATOR TO THE PANEL OCPD MUST NOT BE LESS THAN | | | 115% OF THE NAMEPLATE RATING OF THE GENERATOR. | | | I=KW/(E*1.732), I= 60*1000/(480*1.732), I=60000/831, | | | I=72 AMP | | | AS PER NEC 310.15(B), MORE THAN THREE CURRENT CARRYING | | | CONDUCTORS, DERATE TO 80% | | | F-4 FEEDER NOT ADEQUATE. |
|