Plan Review Notes
Plan Review Notes For Permit 13120817
Permit Number 13120817
Review Stop E
Sequence Number 1
Notes
Date Text
2014-01-28 18:19:11THIS IS BEING CONDITIONALLY APPROVED AS FOLLOWS:
 AS PER NEC 445.13 THE AMPACITY OF THE CONDUCTOR FROM
 THE GENERATOR TO THE PANEL OCPD MUST NOT BE LESS THAN
 115% OF THE NAMEPLATE RATING OF THE GENERATOR.
 I=KW/(E*1.732), I= 60*1000/(480*1.732), I=60000/831,
 I=72 AMP
 AS PER NEC 310.15(B), MORE THAN THREE CURRENT CARRYING
 CONDUCTORS, DERATE TO 80%
 F-4 FEEDER NOT ADEQUATE.