| Plan Review Notes For Permit 13120815 |
| Permit Number |
13120815 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-01-03 15:21:08 | PROVISO: | | | SHEET M1.1 INDICATES IN THE DIFFUSER SCHEDULE SUPPLY | | | GRILLE AD-2 300 CFM IN THE STOREROOM, WALL HEIGHT TO | | | DECK ABOVE, NO | | | RETURN AIR, PLEASE SHOW COMPLIANCE WITH 2010 FBC-M | | | 601.4 BALANCED RETURN. | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|