| Plan Review Notes For Permit 13120758 |
| Permit Number |
13120758 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-01-22 19:37:37 | THE FOLLOWING CORRECTIONS SHALL BE MADE TO THE | | | SUBMITTED DRAWING FOR APPROVAL: | | | 1. THE RESTROOM AS SHOWN ON THE PLANS DOES NOT HAVE | | | LIGHT. | | | 2. THE LIGHTING CONTROL DIAGRAMS AND LIGHTING SCHEDULES | | | INDICATED AS TO BE ON PAGE E1 IN NON EXISTENT. PROVIDE | | | A LIGHTING CONTROL SCHEMATIC AND A FIXTURE SCHEDULE TO | | | COMPLY WITH FBC-E | | | 3. THE REQUIRED SHOW WINDOW OUTLETS ON PAGE E2 APPEAR | | | AS SPARES ON THE PANEL SCHEDULE | | | 4. THERE IS NO ADA STROBE IN THE RESTROOM | | | 5. THE RISER DIAGRAM AS SUBMITTED DOES NOT MATCH THE | | | PANELS AND SCHEDULES AS PRESENTED. PROVIDE AN ACCURATE | | | RISER DIAGRAM. | | | | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH BLDG. DEPARTMENT | | | (561) 805-6718 | | | |
|