2014-01-22 19:37:37THE FOLLOWING CORRECTIONS SHALL BE MADE TO THE
 SUBMITTED DRAWING FOR APPROVAL:
 1. THE RESTROOM AS SHOWN ON THE PLANS DOES NOT HAVE
 LIGHT.
 2. THE LIGHTING CONTROL DIAGRAMS AND LIGHTING SCHEDULES
 INDICATED AS TO BE ON PAGE E1 IN NON EXISTENT. PROVIDE
 A LIGHTING CONTROL SCHEMATIC AND A FIXTURE SCHEDULE TO
 COMPLY WITH FBC-E
 3. THE REQUIRED SHOW WINDOW OUTLETS ON PAGE E2 APPEAR
 AS SPARES ON THE PANEL SCHEDULE
 4. THERE IS NO ADA STROBE IN THE RESTROOM
 5. THE RISER DIAGRAM AS SUBMITTED DOES NOT MATCH THE
 PANELS AND SCHEDULES AS PRESENTED. PROVIDE AN ACCURATE
 RISER DIAGRAM.
  