| Plan Review Notes For Permit 13120731 |
| Permit Number |
13120731 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-01-27 10:09:05 | PASS PROVISO | | | 1) THE EXHAUST SYSTEM MUST BE DESIGNED TO OPERATE WITH | | | A STATIC FLUE PRESSURE | | | BETWEEN NEGATIVE .15 IN. WG AND POSITIVE 0.25 IN. WG. | | | AT THE EXHAUST OF THE | | | ROASTER WHILE IN OPERATION. PROVIDE EQUIPMENT TO TEST | | | WG AT FINAL INSPECTION. | | | 2) SEPARATE PERMIT REQUIRED FOR PLUMBING (GAS LINE) | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|