2013-12-31 08:31:342010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN 170 MPH VULT EXPOSURE D
 THE MEAN ROOF HEIGHT IS SPECIFIED AS 14 FEET AND HAS A
 3/12 SLOPE. THE REQUIRED UPLIFT PRESSURE IN ROOF ZONE 3
 (CORNERS) IS -109 PSF. THE MAXIMUM UPLIFT DESIGN
 PRESSURE LISTED IN THE PRODUCT APPROVAL FOR THE 0.032"
 THICK ALUMINUM IS -101.0 PSF.
  
 2) SUBMIT 2 SETS OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9N-3 FOR THE FLAT DECK. SUBMIT SIGNED AND
 SEALED RAS 117 CALCULATIONS FOR ENHANCED FASTENING IF
 REQUIRED TO MEET UPLIFT PRESSURES. THE REQUIRED UPLIFT
 PRESSURES ARE -116.3 PSF FOR A FLAT ROOF IN EXPOSURE D
 WITH A MEAN ROOF HEIGHT OF 15 FEET. FBC R301.2.1
  