| Plan Review Notes For Permit 13120695 |
| Permit Number |
13120695 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-12-31 08:31:34 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE STRUCTURE IS LOCATED IN 170 MPH VULT EXPOSURE D | | | THE MEAN ROOF HEIGHT IS SPECIFIED AS 14 FEET AND HAS A | | | 3/12 SLOPE. THE REQUIRED UPLIFT PRESSURE IN ROOF ZONE 3 | | | (CORNERS) IS -109 PSF. THE MAXIMUM UPLIFT DESIGN | | | PRESSURE LISTED IN THE PRODUCT APPROVAL FOR THE 0.032" | | | THICK ALUMINUM IS -101.0 PSF. | | | | | | 2) SUBMIT 2 SETS OF PRODUCT APPROVALS AS REQUIRED BY | | | DCA RULE 9N-3 FOR THE FLAT DECK. SUBMIT SIGNED AND | | | SEALED RAS 117 CALCULATIONS FOR ENHANCED FASTENING IF | | | REQUIRED TO MEET UPLIFT PRESSURES. THE REQUIRED UPLIFT | | | PRESSURES ARE -116.3 PSF FOR A FLAT ROOF IN EXPOSURE D | | | WITH A MEAN ROOF HEIGHT OF 15 FEET. FBC R301.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|