Plan Review Notes
Plan Review Notes For Permit 13120685
Permit Number 13120685
Review Stop B
Sequence Number 1
Notes
Date Text
2013-12-26 15:43:44BUILDING PLAN REVIEW
 REVISION: 13120685
 PERMIT: 13100421
 ADD: 800 N FLAGLER DR
 CONT: SEASHORE BUILDING CO.
 TEL: (561)308-9484
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURSDAY DEC. 26/ 2013
 ACTION: DENIED
  
 1) NOTE THE ORIGINAL PERMIT DID NOT SHOW ANY WORK BE
 ING COMLETED IN THE EXISTING RESTROOMS. THIS REVISION
 NOW SHOWS THE INTENT OF WORK BEING COMPLETED IN THE
 MENS RESTROOM, A LEVEL TWO ALTERATION AND WILL NEED TO
 COMPLY WITH 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING AND 2010 FL EXST
 BLDG CODE 706.1 GENERAL. A BUILDING, FACILITY, OR
 ELEMENT THAT IS ALTERED SHALL COMPLY WITH THE
 PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 THE ORIGINAL CONTRACT INDICATES A VALUE OF $35,000.00
 SINCE THERE IS AN ACCESSIBLE ENTRANCE, AN ACCESIBLE
 ROUTE TO ALTERED AREAS, THE NEXT ITEM ON THE LIST FOR
 ACCESSBILE UPGRADES IS RESTROOMS, PLEASE PROVIDE HOW
 20% OR $7,000.00 DOLLARS WILL BE SPENT IN MAKING THE
 RESTROOM A FL ACCESSBLE RESTROOM MEETING THE
 REQUIREMENTS OF;
  
 2010 FBC ACCESSIBILITY 604.3.2.NO OTHER FIXTURES OR
 OBSTRUCTIONS SHALL BE LOCATED WITHIN THE REQUIRED WATER
 CLOSET CLEARANCE.
  
 2010 FBC ACCESSIBILITY 606.1-.5 LAVATORIES
  
 2010 FBC ACCESSIBILITY URINALS 605.3 CLEAR FLOOR SPACE.
 A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305
 POSITIONED FOR FORWARD APPROACH SHALL BE PROVIDED.
  
 605.4 FLUSH CONTROLS.
 FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
  
 2010 FBC ACCESSIBILITY 608.2.1 TRANSFER TYPE SHOWER
 COMPARTMENTS. TRANSFER TYPE SHOWER COMPARTMENTS SHALL
 BE 36 INCHES (915 MM) BY 36 INCHES (915 MM) CLEAR
 INSIDE DIMENSIONS MEASURED AT THE CENTER POINTS OF
 OPPOSING SIDES AND SHALL HAVE A 36 INCH (915 MM) WIDE
 MINIMUM ENTRY ON THE FACE OF THE SHOWER COMPARTMENT.
 CLEARANCE OF 36 INCHES (915 MM) WIDE MINIMUM BY 48
 INCHES (1220 MM) LONG MINIMUM MEASURED FROM THE CONTROL
 WALL SHALL BE PROVIDED.
  
 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING.FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
 .