| 2014-01-03 12:19:39 | MECHANICAL PLAN REVIEW |
| | PERMIT:13120624 |
| | ADD: 1741 PALM BCH LAKES # F03 |
| | CONT: TBD |
| | TEL: (561) |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE:01/03/2014 |
| | ACTION: BUILDING APPROVED WITH EXCEPTION! |
| | |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | MECHANICAL SHEET M-1 SHOWS EF-1 & EF-2 BOTH EXHAUSTING |
| | INTO EXISTING 30X20 EXHAUST DUCT PART OF THE SHELL |
| | BUILDING. |
| | 1) BACK DRAFT DAMPERS REQUIRED, 2010 FBC-M 505.4 & 2010 |
| | FBC-ENERGY 503.2.4.4. |
| | |
| | 2) PLEASE CORRECT FAN SCHEDULE FOR BOTH MODEL AND AIR |
| | FLOW TO CORRELATE WITH MECHANICAL PLAN. 2010 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION, 2010 107.2.1.3 ADDITIONAL |
| | INFORMATION REQUIRED, DISCREPANCY. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |