| Plan Review Notes For Permit 13120574 |
| Permit Number |
13120574 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-01-29 13:38:37 | THE FOLLOWING ITEMS SHALL BE ADDRESSED AND RESUBMIT FOR | | | REVIEWS> | | | 1. NEC 600.05 REQUIRES A SIGN OUTLET BY EVERY ENTRY | | | DOOR | | | 2. NEC 210.62 REQUIRES A SHOW WINDOW LIGHTING OUTLET | | | FOR EVERY 12 LINEAR FOOT OF WINDOW. | | | 3. NEC 110.16 REQUIRES ARC-FLASH WARNING LABELS AT THE | | | ELECTRICAL PANELS | | | 4. NEC 210.08 REQUIRES THAT ALL OUTLETS WITHIN 6' OF | | | THE SINK BE GFCI PROTECTED. | | | 5. MISSING PANEL SCHEDULE AND LOAD CALCS FOR PANEL "B" | | | LIGHTING CONDITIONS AS STATED ON THE DRAWINGS DO NOT | | | SEEM TO COMPLY WITH THE MINIMUM REQUIREMENTS OF THE | | | FBC-ENERGY CONSERVATION CODE SECTION 505 | | | THE EMERGENCY LIGHTING AS SHOWN ON THE PLANS DO NOT | | | COMPLY WITH THE MINIMUM REQUIREMENTS OF NFPA 101 | | | SECTION 7.9 | | | | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH BLDG. DEPARTMENT | | | (561) 805-6718 | | | |
|