| Notes |
| Date |
Text |
| 2013-12-18 21:08:28 | FAILED | | | | | | 1) THE FLOOR PLANS FOR THIS PERMIT DO NOT MATCH THE | | | LANDLORD SHELL PERMIT. THE BAY HAS BEEN EXPANDED TO THE | | | NORTH AND THERE IS A BATHROOM NOT SHOWN. EITHER PROVIDE | | | A LETTER FROM THE LANDLORD THAT THEY WILL REFLECT THESE | | | CHANGES ON A REVISION TO THEIR SHELL PLAN OR PROVIDE | | | DEMOLITION PLANS FOR THE RECONFIGURED INTERIOR. | | | | | | 2) THE MECHANICAL PLANS ONLY SHOW ONE RTU OVER THIS | | | BAY, BUT THE LANDLORD SHELL PLANS SHOW A 12.5 AND A 6 | | | TON UNIT ABOVE THIS SPACE. PLEASE EXPLAIN WHAT HAPPENS | | | TO THESE UNITS AND THE DUCT WORK TO THESE UNITS. | | | | | | 3) SIGNS REQUIRE SPEARATE PERMITS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | 2013-12-18 11:06:39 | 12/18/13 |
|