2013-12-18 21:08:28FAILED
  
 1) THE FLOOR PLANS FOR THIS PERMIT DO NOT MATCH THE
 LANDLORD SHELL PERMIT. THE BAY HAS BEEN EXPANDED TO THE
 NORTH AND THERE IS A BATHROOM NOT SHOWN. EITHER PROVIDE
 A LETTER FROM THE LANDLORD THAT THEY WILL REFLECT THESE
 CHANGES ON A REVISION TO THEIR SHELL PLAN OR PROVIDE
 DEMOLITION PLANS FOR THE RECONFIGURED INTERIOR.
  
 2) THE MECHANICAL PLANS ONLY SHOW ONE RTU OVER THIS
 BAY, BUT THE LANDLORD SHELL PLANS SHOW A 12.5 AND A 6
 TON UNIT ABOVE THIS SPACE. PLEASE EXPLAIN WHAT HAPPENS
 TO THESE UNITS AND THE DUCT WORK TO THESE UNITS.
  
 3) SIGNS REQUIRE SPEARATE PERMITS.
  