Notes
Date Text
2013-12-27 12:49:23PLAN DENIED
 1) PROVIDE A PLAN SHOWING GREASE DUCT,
 PER SECTION 107 FBC 2010
 2) PROVIDE A DETAIL FROM THE ENGINEER ON
 HOW THE EXHAUST FAN CURB IS TIED TO ROOF.
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 3) AIR CONDITIONING PLANS, COOLER AND HOOD SUPPRESSION
 REQUIRE SEPARATE APPLICATION, PLAN AND PERMITS