| Plan Review Notes For Permit 13120547 |
| Permit Number |
13120547 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-01-14 12:26:24 | THIS APPLICATION WAS CONDITIONALLY APPROVED AS FOLLOWS: | | | 1. THE SUBMITTED PLANS CALL FOR CIRCUIT WIRING USING | | | THHN CONDUCTORS. THIS MAY BE TRUE FOR THOSE SIGNS | | | MOUNTED ON THE FACADE AS THOSE PLACED AWAY FROM THE | | | BLDG. WILL HAVE TO COMPLY WITH THE REQUIREMENTS OF NEC | | | 300.5(B) WHICH CALLS FOR CONDUCTORS LISTED FOR WET | | | LOCATIONS | | | 2. THIS SIGN SHALL COMPLY WITH ALL THE REQUIREMENTS OF | | | THE FBC-E SECTION 505. | | | | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH BLDG. DEPARTMENT | | | (561) 805-6718 | | | | | | | | | |
|