2013-12-23 14:41:07854 CONNISTON
 PERMIT # 13120531
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER NFPA 24, BUILDINGS LESS THAN 40 FT IN HEIGHT, A
 BACKFLOW PREVENTER SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FT BUT AT LEAST AS FAR FROM THE BUILDING
 AS THE HEIGHT OF THE WALL FACING THE BACKFLOW
 PREVENTER. NOTE, EXCEPTION TO BE MADE DUE TO EXISTING
 BUILDING.
  
 PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR
 SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
  
  
 LAUREN PHILMORE
 FIRE INSPECTOR II / INVESTIGATOR I
 OFFICE OF THE FIRE MARSHAL