| Plan Review Notes For Permit 13120531 |
| Permit Number |
13120531 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-23 14:41:07 | 854 CONNISTON | | | PERMIT # 13120531 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PER NFPA 24, BUILDINGS LESS THAN 40 FT IN HEIGHT, A | | | BACKFLOW PREVENTER SHALL BE PERMITTED TO BE INSTALLED | | | CLOSER THAN 40 FT BUT AT LEAST AS FAR FROM THE BUILDING | | | AS THE HEIGHT OF THE WALL FACING THE BACKFLOW | | | PREVENTER. NOTE, EXCEPTION TO BE MADE DUE TO EXISTING | | | BUILDING. | | | | | | PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR | | | SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN | | | POSITION. | | | | | | PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT | | | CONNECTION. | | | | | | PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE | | | DEPARTMENT CONNECTION. | | | | | | | | | | | | LAUREN PHILMORE | | | FIRE INSPECTOR II / INVESTIGATOR I | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4783 | | | |
|