| Notes |
| Date |
Text |
| 2013-12-27 15:48:59 | BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | | | | 1) SHEET LS-2 RED LINED, TO KEEP EXIT LIGHT AT | | | STAIRWELL 4.2, I SPOKE WITH THE DESIGNER OF RECORD TED | | | DAVIS ABOUT THIS HE WAS OK WITH THE RED LINING TO KEEP | | | THE EXIT LIGHT. | | | | | | 2) A REVISION IS REQUIRED, NO PRODUCT APPROVALS WERE | | | SUBMITTED, PRESSURES ARE OK. WE WILL NEED PRODUCT | | | APPROVALS FOR STOREFRONT GLAZING, EXTERIOR GLAZED DOORS | | | WITH PANIC HARDWARE. 2010 FBC-B 1008.1.10 REQUIRES | | | PANIC HARDWARE WITH AN ASSEMBLY OCUPANCY OVER 50 | | | OCCUPANTS. | | | | | | 3) ALL EXIT DOORS WILL REQUIRE PANIC HARDWARE 2010 | | | FBC-B 1008.1.10. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|