| Plan Review Notes For Permit 13120508 |
| Permit Number |
13120508 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-17 18:02:39 | AS PREVIOUSLY INFORMED, YOU SHALL PROVIDE LOAD | | | CALCULATIONS FOR THE PROPOSED USE OF OCCUPANCY. HENCE: | | | GENERAL LIGHTING LOADS FOR OFFICE TO BE CALCULATED AT | | | 3.5 W/SQ. FT. | | | YOU SHALL PROVIDE DETAILS ON THE EXISTING ELECTRICAL | | | PANELS AND SERVICE. | | | YOU SHALL PROVIDE THE REQUIRED DISCONNECTS FOR THE | | | WATER HEATER AND A/C UNIT. | | | PROVIDE A CLEAR AND LEGIBLE PLAN AS REQUIRED BY FBC 107 | | | |
|