| 2014-05-19 17:18:20 | RESIDENTIAL (R3) GARAGE CONVERSION, THIRD CHECKLIST. |
| | CODE: 2010 FBC. |
| | |
| | 1- WINDOWS AND DOORS PRODUCT APPROVALS SUBMITTED NOW |
| | ARE FOR VINYL PRODUCTS. THIS TYPE OF WINDOWS AND DOORS |
| | ARE NOT APPROVED BY HISTORIC. NEED TO PROVIDE PRODUCT |
| | APPROVAL (2 COPIES) AS REQUIRED BY DCA RULE 9N-3 FOR |
| | ANOTHER WINDOWS AND DOORS THAT ARE ACCEPTABLE FOR |
| | HISTORIC. SEE HISTORIC COMMENTS. |
| | |
| | ***NOTE: IF NEW PRODUCT APPROVALS SUBMITTED ARE FOR |
| | NON-IMPACT WINDOWS AND DOORS, THEN NEED TO PROVIDE |
| | STORM SHUTTERS PRODUCT APPROVAL AND COMPLETE |
| | INSTALLATION SCHEDULE. |
| | |
| | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ABOVE PRODUCT APPROVALS. SEC. 107.3.4.1 OF CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 3- THE BEDROOM WINDOW DOESN'T COMPLY WITH THE EGRESS |
| | REQUIREMENTS OF SEC. R310.1.2 OF 2010 FBC-RESIDENTIAL. |
| | 48"X48" SINGLE HUNG WINDOW DOESN'T PROVIDE THE REQUIRED |
| | 24" MIN. CLEAR HEIGHT. REVISE AS REQUIRED. |
| | |
| | 4- A) PROVIDE COMPLETE FRAMING DETAILS FOR THE NEW |
| | EXTERIOR OPENINGS, INCLUDING THE NEW DOUBLE FRENCH |
| | DOORS. SEC. R301.1. (REPEAT COMMENT. NOT ADDRESSED. |
| | ONLY DETAIL FOR WINDOW FRAMING WAS PROVIDED). |
| | |
| | B) NEW FRENCH DOORS OPENING: SPECIFY MASONRY OPENING |
| | VERTICAL REINFORCEMENT AS REQUIRED BY SEC. R609.3.2. |
| | (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | C) PROVIDE COMPLETE STRUCTURAL BUCK DETAIL FOR NEW |
| | FRENCH DOORS AS REQUIRED BY SEC. R612.10.2.1. ***NOTE: |
| | BUCK SPECIFIED NEEDS TO PROVIDE FULL SUPPORT TO THE |
| | DOOR FRAME. (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | 5- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE |
| | DUE. THEN, BRING BACK COUNTY STAMPED PLANS AND COPY OF |
| | PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY |
| | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| | CODE. (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | 6- SCOPE OF WORK IS TO CONVERT GARAGE TO LIVING SPACE, |
| | NOT TO REPLACE WINDOWS/DOORS AND MOVE BATHROOM |
| | LOCATION. VALUATION DECLARED IN THE PERMIT APPLICATION |
| | IS TOO LOW. UPDATE VALUATION TO INCLUDE ALL LABOR, |
| | MATERIALS, CONTRACTOR'S OVERHEAD/ PROFIT AND ALL DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 OF CITY |
| | AMENDMENTS. (REPEAT COMMENT. NOT ADDRESSED) |
| | |
| | ***NOTES: |
| | *PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |