| 2014-01-16 09:03:33 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- ENGINEER NEEDS TO USE CURRENT APPROVED SEAL AS |
| | REQUIRED BY SEC. 61G15-23.001 OF FLORIDA ADMINISTRATIVE |
| | CODE AND CHAPTER 471 FLORIDA STATUTE. CURRENT SEAL TO |
| | SAY "LICENSE" NOT CERTIFICATE". |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) FRENCH DOORS. NOA 08-0312.12 SUBMITTED EXPIRED ON |
| | MAY 25, 2011. NEED TO PROVIDE CURRENT NOA. |
| | |
| | B) SINGLE HUNG WINDOWS. NOA 06-0705.02 SUBMITTED |
| | EXPIRED ON JULY 12, 2011. NEED TO PROVIDE CURRENT NOA. |
| | |
| | C) HURRICANE SHUTTERS FOR WINDOWS AND DOORS THAT DON'T |
| | HAVE IMPACT GLAZING. |
| | |
| | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL THE PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. |
| | |
| | 4- HURRICANE SHUTTERS: PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE ( SEE CITY SAMPLE OF INSTALLATION SCHEDULE OR |
| | PROVIDE ANOTHER FORMAT THAT PROVIDES ALL THE |
| | INFORMATION). |
| | ***NOTE: CLEARLY IDENTIFY SPECIFIC MOUNTING CONDITIONS |
| | AND SPECIFIC ANCHOR TYPE AND SPACING TO BE USED. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 5- SHEET C-1: |
| | A) THE CURRENT CODE IS THE 2010 FBC, NOT THE 2007 FBC. |
| | REVISE AL THE INFORMATION ON PLANS THAT IS REFERENCING |
| | THE 2007 FBC. |
| | |
| | B) SPECIFY THE WIND DESIGN LOADS: ULTIMATE WIND SPEED |
| | AND THE NOMINAL WIND SPEED AS REQUIRED BY SEC. |
| | R301.2.1.3 OF 2010 FBC-RESIDENTIAL. |
| | |
| | C) SPECIFY THE BUILDING EXPOSURE. ACCORDING TO SEC. |
| | R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL, THIS BUILDING IS |
| | LOCATED IN EXPOSURE "C" NOT "B". COORDINATE WITH ITEM |
| | #7 BELOW. |
| | |
| | 6- SHEET A-2: |
| | A) SHOW COMPLIANCE WITH THE EGRESS REQUIREMENTS FOR THE |
| | BEDROOM AS REQUIRED BY SEC. R310 OF 2010 |
| | FBC-RESIDENTIAL. (NOTE: SHEET A-1 SHOWS EXISTING |
| | BEDROOM, THERE ARE NO PERMITS ON CITY RECORDS FOR THE |
| | CONVERSION). |
| | |
| | B) PROVIDE COMPLIANCE WITH THE HEATING REQUIREMENTS OF |
| | SEC. R303.8 OF 2010 FBC-RESIDENTIAL. |
| | |
| | C) PROVIDE COMPLETE FRAMING DETAILS FOR THE NEW |
| | EXTERIOR OPENINGS, INCLUDING THE NEW DOUBLE FRENCH |
| | DOORS. SEC. R301.1. |
| | |
| | D) SPECIFY OPENINGS VERTICAL REINFORCEMENT AS REQUIRED |
| | BY SEC. R609.3.2. |
| | |
| | E)REVISE EXTERIOR FRENCH DOORS NOTE #2. CURRENT ASCE IS |
| | ASCE 7-10 NOT ASCE 7-05. ALSO, REVISE THE WIND SPEED, |
| | EXPOSURE AND THE OPENINGS DESIGN PRESSURES. COORDINATE |
| | WITH ITEM # 5 ABOVE. |
| | ***NOTE: SAME COMMENT APPLIES TO WINDOWS NOTES. REVISE |
| | AS REQUIRED. |
| | |
| | 7- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE |
| | DUE. THEN, BRING BACK COUNTY STAMPED PLANS AND COPY OF |
| | PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY |
| | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| | CODE. |
| | |
| | 8- SCOPE OF WORK IS TO CONVERT GARAGE TO LIVING SPACE, |
| | NOT TO REPLACE WINDOWS/DOORS AND MOVE BATHROOM |
| | LOCATION. VALUATION DECLARED IN THE PERMIT APPLICATION |
| | IS TOO LOW. UPDATE VALUATION TO INCLUDE ALL LABOR, |
| | MATERIALS, CONTRACTOR'S OVERHEAD/ PROFIT AND ALL DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 OF CITY |
| | AMENDMENTS. |
| | |
| | ***NOTES: |
| | *PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |