Date Text
2013-12-17 19:31:54THE ADDED LOAD OF THE TWO EXIT EMERGENCY LIGHTS DO NOT
 WARRANT ADDITIONAL SUBMISSION OF LOAD CALCS,
 THESE LIGHTS SHALL BE CONNECTED TO AN UNSWITCHED SOURCE
 AHEAD OF ANY LIGHTING CONTROL DEVICES.