| 2014-04-09 12:03:55 | BUILDING PLAN REVIEW |
| | PERMIT: 13120456 |
| | ADD: 424 PALM ST |
| | CONT: COMET & ELECTRIC |
| | TEL: (561) 689-4400 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WED. APRIL 09/ 2014 |
| | ACTION: DENIED |
| | |
| | 1-2) COMPLIED. |
| | 2) THE SURVEY DOES NOT INDICATE WHERE THE LOCATION OF |
| | THE NEW GENERATOR WILL BE LOCATED. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 3) 2ND REVIEW, TYPICAL GENERATOR PAD DETAILS ARE BY |
| | DAVID CARMO P. E.. PLANS ARE COPIED NOT SIGNED NOR |
| | SEALED. |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | EFFECTIVE DATE 05/06/2009 |
| | THE PLANS DO NOT SHOW HOW THE GENERATOR WILL BE |
| | ANCHORED TO RESIST, SLIDDING AND THE MOMENT OF |
| | OVERTURNING, NOR IS THERE PLANS INCLUDED SHOWING A |
| | FOUNDATION/ SLAB AND REINFORCEMENT NOR WIND DESIGN |
| | CRITERIA. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED, |
| | MWFRS (MAIN WIND FORCE RESISTING SYSTEM FOR MOMENT OF |
| | OVERTURNING. |
| | |