| Plan Review Notes For Permit 13120454 |
| Permit Number |
13120454 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-23 15:02:00 | 626 PALM ST | | | PERMIT #13120454 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE TOTAL PERMIT JOB VALUE NEEDS TO INCLUDE MATERIALS | | | AND LABOR. | | | | | | PLAN STATES BATTERY CALCULATIONS ARE MISSING FROM | | | PERNIT PACKAGE | | | | | | THIS APPEARS TO BE A ZONED PANEL. ZONES ARE NOT DENOTED | | | ON PLAN | | | | | | APPLIANCES SHOWN ON PLAN DO NOT INCLUDE THE CANDELA | | | BEING USED. | | | | | | WIRING DIAGRAM IS MISSING FROM PERMIT PACKAGE. | | | | | | END OF THE LINE RESISTORS NOT SHOWN ON PLAN. | | | | | | | | | LAUREN PHILMORE | | | FIRE INSPECTOR II / INVESTIGATOR I | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4783 | | | | | | |
|