| Plan Review Notes For Permit 13120425 |
| Permit Number |
13120425 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-01-22 13:08:12 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE ROOF | | | A/C STAND HAS BEEN CLOSED BY MIAMI-DADE AND IS NO | | | LONGER ACCEPTABLE. SUBMIT A CURRENT PRODUCT APPROVAL. | | | DCA RULE 9N-3 | | | | | | 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS, INSTALLATION INSTRUCTIONS AND LISTING | | | INFORMATION FOR THE EXHAUST HOOD THAT IS SHOWN ON THE | | | EXTERIOR AT THE COVERED PORCH. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|