2014-01-22 18:04:492010 FBC
  
 DENIED BY BUILDING
  
 1) ON SHEET 3 THE SECTION MARKER FOR A-A IS NOT IN THE
 CORRECT LOCATION ON THE SLAB, BEAM AND COLUMN PLAN
 BASED ON WHAT IS SHOWN IN THE SECTION A-A DETAIL.
 PROVIDE A STRUCTURAL DETAIL SHOWING HOW THE 8" X 12"
 BEAM TIES INTO THE EXTERIOR WALL. IT APPEARS FROM THE
 WAY THIS BEAM IS SHOWN ON THE SLAB, BEAM AND COLUMN
 PLAN THAT THERE IS A WALL AND A COLUMN UNDER THE 8" X
 12" TIE BEAM. PLEASE CLARIFY.
  
 2) THE MULE-HIDE SELF ADHERED ROOFING PRODUCT APPROVAL
 THAT WAS SUBMITTED FOR THE FLAT ROOF IS FOR A STEEL
 DECK. SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 FLAT ROOF THAT IS FOR A WOOD DECK AS REQUIRED BY DCA
 RULE 9N-3. IF THE DESIGN PRESSURE FOR THE SYSTEM IS
 LESS THAN THE - 96 PSF REQUIRED AT THE CORNERS OF THE
 FLAT ROOFS, SUBMIT TWO SETS OF SIGNED AND SEALED RAS
 117 CALCULATIONS FOR ENHANCED FASTENING OF THE BASE
 SHEET.
  