| Plan Review Notes For Permit 13120425 |
| Permit Number |
13120425 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-17 09:44:53 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) THE ENERGY CALCULATIONS AND EQUIPMENT SIZING | | | CALCULATIONS ARE FOR WORST CASE. THE 2010 FBC ENERGY | | | CONSERVATION SECTION 403.6.1 REQUIRES EQUIPMENT LOAD | | | CALCULATIONS TO BE BASED ON THE BUILDING LOADS FOR THE | | | DIRECTIONAL ORIENTATION OF THE BUILDING. PLEASE SUBMIT | | | LOAD CALCULATIONS THAT ARE BASED ON THE ACTUAL | | | DIRECTIONAL ORIENTATION OF THE BUILDING. | | | | | | 2) THE HEATING AND COOLING EQUIPMENT SPECIFIED ON THE | | | PLANS IS REQUIRED TO MATCH THE EQUIPMENT SIZING | | | CALCULATIONS AND THE ENERGY CALCULATIONS. FBC ENERGY | | | CONSERVATION SECTION 403.6.1 AND CITY AMENDMENTS | | | 107.2.1 | | | | | | 3) THE ENERGY CALCULATION FORM WAS NOT SIGNED BY THE | | | OWNER/AGENT. FBC ENERGY CONSERVATION SECTION 405.4 | | | | | | 4) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE ROOF | | | TOP A/C STANDS AS REQUIRED BY DCA RULE 9N-3 AND FBCR | | | M1307.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|