2013-12-17 09:44:532010 FBC
  
 DENIED BY MECHANICAL
  
 1) THE ENERGY CALCULATIONS AND EQUIPMENT SIZING
 CALCULATIONS ARE FOR WORST CASE. THE 2010 FBC ENERGY
 CONSERVATION SECTION 403.6.1 REQUIRES EQUIPMENT LOAD
 CALCULATIONS TO BE BASED ON THE BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. PLEASE SUBMIT
 LOAD CALCULATIONS THAT ARE BASED ON THE ACTUAL
 DIRECTIONAL ORIENTATION OF THE BUILDING.
  
 2) THE HEATING AND COOLING EQUIPMENT SPECIFIED ON THE
 PLANS IS REQUIRED TO MATCH THE EQUIPMENT SIZING
 CALCULATIONS AND THE ENERGY CALCULATIONS. FBC ENERGY
 CONSERVATION SECTION 403.6.1 AND CITY AMENDMENTS
 107.2.1
  
 3) THE ENERGY CALCULATION FORM WAS NOT SIGNED BY THE
 OWNER/AGENT. FBC ENERGY CONSERVATION SECTION 405.4
  
 4) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE ROOF
 TOP A/C STANDS AS REQUIRED BY DCA RULE 9N-3 AND FBCR
 M1307.2.1
  