Plan Review Notes
Plan Review Notes For Permit 13120425
Permit Number 13120425
Review Stop B
Sequence Number 1
Notes
Date Text
2013-12-17 16:04:092010 FBC
  
 DENIED BY BUILDING
  
 1) THE ENGINEER NEEDS TO EVALUATE THE STRUCTURAL DESIGN
 SPECIFIED AT THE EXTERIOR WALL FOR THE 8 X 12 CONCRETE
 BEAM WITH (4) # 4 BARS SHOWN IN SECTION A - A ON SHEET
 3 AND PROVIDE CALCULATIONS. THE PLANS SHOW 2 FILLED
 CONCRETE BLOCK AT THE EXTERIOR WALL RATHER THAN A
 FORMED AND POURED CONCRETE COLUMN LIKE THE ONE ON THE
 OTHER END. CITY AMENDMENTS 107.2.1.3 NOTE: RATHER THAN
 HAVE A BEAM BELOW THE CEILING, THIS BEAM COULD BE
 ELIMINATED BY USING ROOF GIRDER TRUSSES TO HANG THE
 EXISTING AND NEW TRUSSES ON.
  
 2) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 LARGE MISSILE IMPACT RATED EXTERIOR DOORS AND WINDOWS
 DO NOT HAVE THE DBPR APPROVED INSTALLATION AND
 EVALUATION INFORMATION ATTACHED TO THE FLORIDA FL#
 COVER-SHEETS. THEY ALL HAVE MIAMI-DADE NOAS AS THEIR
 APPROVED INFORMATION. THIS IS THE LINK TO THE FLORIDA
 PRODUCT APPROVAL WEB SITE WHERE YOU CAN PRINT OUT THE
 APPROVED INFORMATION THAT IS REQUIRED TO BE SUBMITTED
 BY DCA RULE 9N-3.
 HTTP://FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX
  
 3) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 ROOTING MATERIAL THAT WILL BE INSTALLED ON THE FLAT
 ROOF. SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS FOR ENHANCED FASTENING AT THE PERIMETER
 AND CORNER ROOF AREAS IF THE MAXIMUM DESIGN PRESSURES
 FOR THE SELECTED SYSTEM FROM THE PRODUCT APPROVAL ARE
 NOT ADEQUATE FOR THESE AREAS. FBC R301.2.1.
  
 4) SPECIFY THE METHOD OF ATTACHMENT FROM THE ROOF TILE
 PRODUCT APPROVAL THAT WILL BE USED TO INSTALL IT AND
 RESIST THE REQUIRED OVERTURN MOMENT. IF A ROOF TILE
 ADHESIVE WILL BE USED SUBMIT TWO COPIES OF IT'S PRODUCT
 APPROVALS THAT HAVE BEEN APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. DCA RULE 9N-3 AND CITY AMENDMENTS
 107.3.4.1
  
 5) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 STRUCTURAL WINDOW MULLIONS AND THE SIMPSON CONNECTORS
 THAT WILL BE USED AND THAT HAVE BEEN APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. DCA RULE 9N-3 AND
 CITY AMENDMENTS 107.3.4.1
  
 6) SUBMIT TWO COPIES OF THE ICC-ES EVALUATION REPORT
 FOR THE ICYNENE SPRAY FOAM INSULATION. CITY AMENDMENTS
 107.2.1.3
  
 7) THE PLANS SPECIFY A 4' 0" X 6' 8" EXTERIOR SLIDING
 GLASS DOOR AT THE LAUNDRY. THIS IS NOT A STANDARD SIZE
 SLIDING GLASS DOOR AND WOULD PROVIDE AN OPENING LESS
 THAN 2 FEET WIDE. PLEASE CLARIFY IF THIS IS YOUR
 INTENT. CITY AMENDMENTS 107.2.1 THE SMALLEST SGD WIDTH
 ON THE PRODUCT APPROVAL THAT WAS SUBMITTED IS 5 FEET.
  
 8) TWO SETS OF PLANS ARE REQUIRED PER CITY AMENDMENTS
 107.1. ONLY ONE ROOF FRAMING PLAN WAS SUBMITTED. SUBMIT
 AN ADDITIONAL PLAN SHEET T-1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]