| Notes |
| Date |
Text |
| 2013-12-26 08:26:59 | 6651 NORTH JOG ROAD - TURBINE GENERATOR | | | TRACKING #13120411 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVISO - SUBMIT REVISION | | | | | | HOSE REEL WITH 1-1/2" HOSE VALVES APPEAR TO HAVE | | | PRESSURES THAT WILL EXCEED 100 PSI. PER NFPA 14 SECTION | | | 7.2.3.1, WHERE THE RESIDUAL PRESSURE AT A 1-1/2" OUTLET | | | ON A HOSE CONNECTION AVAILABLE FOR TRAINED PERSONNEL | | | USE EXCEEDS 100 PSI, AN APPROVED PRESSURE-REGULATING | | | DEVICE SHALL BE PROVIDED TO LIMIT THE RESIDUAL PRESSURE | | | TO 100 PSI. ALSO PER NFPA 14 SECTION 7.2.3.2, AN | | | APPROVED PRESSURE-REGULATING DEVICE SHALL BE PROVIDED | | | TO LIMIT STATIC AND RESIDUAL PRESSURES AT THE OUTLET OF | | | THE HOSE CONNECTION TO 100 PSI FOR 1-1/2" HOSE | | | CONNECTIONS AVAILABLE FOR TRAINED PERSONNEL USE AND 175 | | | PSI FOR OTHER HOSE CONNECTIONS. | | | | | | TO AVOID PRESSURE REGULATING DEVICES I WOULD RECOMMEND | | | A TRUE CLASS I STANDPIPE SYSTEM (2-1/2 FDVS ONLY) AND | | | ELIMINATE THE 1-1/2" FDVS WITH HOSE AND REEL BECAUSE | | | FIRE DEPARTMENT PERSONNEL WILL NOT USE THIS EQUIPMENT. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | | | | | | | |
|