| 2013-12-16 13:44:10 | PERMIT #13120304 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | ***PROVISO**** |
| | 1) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION |
| | SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND |
| | RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION |
| | SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A |
| | 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A |
| | FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED |
| | BY EMAIL ([email protected]) OR IN WRITING (FAX: |
| | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE |
| | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? |
| | |
| | 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| | SYSTEM AND/OR FIRE ALARM SYSTEM. |
| | |
| | THE FOLLOWING ITEMS MAY ALREADY BE EXISTING, HOWEVER |
| | THEY ARE NOT INDICATED ON PLANS: |
| | 3) PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | 4) PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING |
| | ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE |
| | ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN |
| | HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE |
| | BACKGROUND. |
| | |
| | 5) PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS |
| | WITH EXIT SIGNS. |
| | |
| | 6) FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN |
| | OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER |
| | THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE |
| | PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER |
| | LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE |
| | RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR |
| | PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE |
| | AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A |
| | READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN |
| | UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS |
| | SHALL BE AT LEAST 1 INCH IN HEIGHT. A THUMB TURN STYLE |
| | LOCK IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED |
| | LOCK. |
| | |
| | |
| | SUE ELLEN CALDERON |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 804-4751 |
| | |
| | |