| Plan Review Notes For Permit 13120266 |
| Permit Number |
13120266 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-01-09 18:36:06 | THIS APPLICATION FAILED THE FIRST REVIEW AS OUTLINED | | | BELOW: | | | 1. PG. 1.1 LIGHTING: AS PER NEC 600.5 EVERY COMMERCIAL | | | BLDG. SHALL HAVE AT LEAST ONE OUTLET FOR SIGNAGE AT | | | EACH ENTRANCE | | | 2. PG. 2.1 POWER PLAN, I WAS UNABLE TO FIND A WATER | | | COOLER WHICH IS USUALLY IN THIS TYPE OF ESTABLISHMENT, | | | NOR COULD I VERIFY IT WITH THE PANEL SCHEDULES. I WAS | | | VERIFYING THAT IT HAD BEEN SERVED WITH A GFI PROTECTED | | | CIRCUIT. | | | 3. PG. 2.2 ROOF POWER PLAN: NEC 210.63 REQUIRES THAT | | | THERE BE A SERVICE OUTLET WITHIN 25' OF THE CONDENSING | | | UNITS. NEC 210.8 REQUIRES THAT THE OUTLET BE GFI | | | PROTECTED. NEC 406.8 REQUIRES THAT THE OUTLET BE "WR" | | | WEATHER RESISTANT RATED AND THAT IT HAVE AN IN-USE TYPE | | | COVER. | | | 4. PG. 3.1 RISER & DETAILS: YOU FAIL TO PROVIDE THE | | | CONDUCTOR INSULATION AND RACEWAY TYPES. | | | 5. PG. 4.1 ELECTRICAL PANEL SCHEDULES: THIS PAGE HAS A | | | MALFUNCTION WHICH DOES NOT LET ME PROPERLY OPEN THE | | | PAGE OR MANEUVER WITHIN THE MINIMIZED VIEW TO PROPERLY | | | REVIEW IT. | | | 6. PG. 5.1 FIRE ALARM: AS NOTED, THIS IS NOT SUFFICIENT | | | DOCUMENTATION OR DESIGN FOR A FIRE ALARM SUBMISSION. AS | | | SEPARATE FIRE ALARM PERMIT AND SUBMITTAL PACKAGE SHALL | | | BE SECURED. |
|