Plan Review Notes
Plan Review Notes For Permit 13120266
Permit Number 13120266
Review Stop E
Sequence Number 1
Notes
Date Text
2014-01-09 18:36:06THIS APPLICATION FAILED THE FIRST REVIEW AS OUTLINED
 BELOW:
 1. PG. 1.1 LIGHTING: AS PER NEC 600.5 EVERY COMMERCIAL
 BLDG. SHALL HAVE AT LEAST ONE OUTLET FOR SIGNAGE AT
 EACH ENTRANCE
 2. PG. 2.1 POWER PLAN, I WAS UNABLE TO FIND A WATER
 COOLER WHICH IS USUALLY IN THIS TYPE OF ESTABLISHMENT,
 NOR COULD I VERIFY IT WITH THE PANEL SCHEDULES. I WAS
 VERIFYING THAT IT HAD BEEN SERVED WITH A GFI PROTECTED
 CIRCUIT.
 3. PG. 2.2 ROOF POWER PLAN: NEC 210.63 REQUIRES THAT
 THERE BE A SERVICE OUTLET WITHIN 25' OF THE CONDENSING
 UNITS. NEC 210.8 REQUIRES THAT THE OUTLET BE GFI
 PROTECTED. NEC 406.8 REQUIRES THAT THE OUTLET BE "WR"
 WEATHER RESISTANT RATED AND THAT IT HAVE AN IN-USE TYPE
 COVER.
 4. PG. 3.1 RISER & DETAILS: YOU FAIL TO PROVIDE THE
 CONDUCTOR INSULATION AND RACEWAY TYPES.
 5. PG. 4.1 ELECTRICAL PANEL SCHEDULES: THIS PAGE HAS A
 MALFUNCTION WHICH DOES NOT LET ME PROPERLY OPEN THE
 PAGE OR MANEUVER WITHIN THE MINIMIZED VIEW TO PROPERLY
 REVIEW IT.
 6. PG. 5.1 FIRE ALARM: AS NOTED, THIS IS NOT SUFFICIENT
 DOCUMENTATION OR DESIGN FOR A FIRE ALARM SUBMISSION. AS
 SEPARATE FIRE ALARM PERMIT AND SUBMITTAL PACKAGE SHALL
 BE SECURED.