| Plan Review Notes For Permit 13120257 |
| Permit Number |
13120257 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-07 10:07:40 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE STRUCTURE IS LOCATED WITHIN 600 FT OF THE | | | INTER-COASTAL WATERWAY AND IS EXPOSURE CATEGORY D. FBC | | | R301.2.1.4.3 SUBMIT REVISED RAS 117 CALCULATIONS. | | | | | | 2) THE PROPERTY APPRAISER'S INFROMATION INDICATES THAT | | | THE ROOF COVERING IS COMPOSITE SHINGLES AND NOT TILE. | | | SUBMITT A SIGNED AND SEALED ENGINEER'S EVALUATION | | | REPORT STATING THE THE EXISTING ROOF STRUCTURE IS | | | CAPABLE OF SAFELY SUPPORTING ALL OF THE LOADS FOR THE | | | PROPOSED TILE ROOF. FBC R301.1 | | | | | | 3) THE 3M RTA-1 FOAM ROOF TILE ADHESIVE IS NOT LISTED | | | AS AN APPROVED TILE ADHESIVE IN THE POLYGLASS | | | UNDERLAYMENT PRODUCT APPROVAL LIMITATIONS ON PAGE 4 OF | | | THE EVALUATION REPORT FOR FL 5259. SEE LIMITATION # | | | 5.4.1 ON PAGE 4 OF 10. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|